Pass 315.4-Outside storage <br /> ✓; Outside storage of combustible materials shall not be located <br /> within 10 feet(3048 mm)of a lot line.Exceptions:1.The <br /> separation distance is allowed to be reduced to 3 feet(914 <br /> mm)for storage not exceeding 6 feet(1829 mm)in height.2. <br /> The separation distance is allowed to be reduced when the <br /> fire code official determines that no hazard to the adjoining <br /> property exists. <br /> Pass 505.1-Address identification <br /> New and existing buildings shall have approved address <br /> numbers.building numbers or approved building <br /> identification placed in a position that is plainly legible and <br /> visible from the street or road fronting the property.These <br /> numbers shall contrast with their background.Address <br /> numbers shall be provided in additional approved locations <br /> to facilitate emergency response.Address numbers shall be <br /> Arabic numbers or alphabetical letters.Numbers shall be a <br /> minimum of 4 inches(101.6 mm)high with a minimum stroke <br /> width of 0.5 inch(12.7 mm).Where access is by means of a <br /> private road and the building cannot be viewed from the <br /> public way,a monument,pole or other sign or means shall be <br /> used to identify the structure.Address numbers shall be <br /> maintained.Exception:Secured sites manned with on site. <br /> full-time 24 hour response teams who escort responding fire <br /> departments may omit address numbers.building numbers or <br /> building identification on individual buildings. <br /> Pass 506.1"-Where required <br /> Whenever the servicing fire department has instituted a key <br /> box emergency access system.a key box compatible with <br /> that system shall be installed in an accessible location if:(1) <br /> The building is protected with an automatic sprinkler system <br /> equipped with a local or transmitted water-flow alarm.or(2) <br /> The building is provided with any fire alarm system equipped <br /> with an outside audible/visual signaling device.or(3)The <br /> building is provided with any fire alarm system where the <br /> alarm is transmitted to an off-site location.or to the fire alarm <br /> center for the servicing fire department. <br /> Pass 506.1.1-Locks <br /> An approved lock shall be installed on gates or similar <br /> barriers when required by the fire code official. <br /> Pass 509.1'-Identification <br /> O✓ Fire protection equipment shall be identified in an approved <br /> manner.Normally closed rooms containing air handling <br /> equipment over 2.000 CFM.rooms containing a water heater <br /> or boiler over 400.000 BTUIHR input.sprinkler risers. <br /> sprinkler control valves.fire alarm control panels.smoke <br /> evacuation system control panels.or control panels for wet <br /> chemical.dry chemical,foam.carbon dioxide and clean agent <br /> systems shall be identified for the use of the servicing fire <br /> department.Approved signs required identifying fire <br /> protection equipment locations shall be constructed of <br /> durable materials.lettering shall be in contrast with the <br /> background and be permanently installed and readily visible. <br /> Pass 509.1.1-Utility identification <br /> (✓! Gas shutoff valves.electric meters,service switches and <br /> other utility equipment shall be clearly and legibly marked to <br /> identify the unit or space that it serves.Identification shall be <br /> made in an approved manner.readily visible and shall be <br /> maintained. <br /> GENERATED ON 3/17/26, 10:39 AM OF 10 <br />