Laserfiche WebLink
ASSUMPTIONS PER SPECIFICATIONS <br />• The softener will be attaching to the system through 2" copper pipes. <br />• New softening system to be installed in the same footprint as existing (obsolete) <br />system as well as is practical. <br />• The system will have sufficient capacity to handle the highest usage levels for <br />the facility. Said usage levels to be determined from the fixture count supplied as <br />part of the RFP. <br />• System will be demand based and not timer based. <br />• System is to use commercially available salt and customer will supply and <br />maintain salt to softening system. <br />• System to include proper set up at installation. <br />• Site will require monthly visits from vendor to monitor softening system and to <br />ensure proper operation. <br />• Customer to oversee softening system operation between vendor visits. <br />WATCON GENERAL ANALYSIS <br />• Service flow for current obsolete system is estimated at 45 gallons per minute, <br />assuming operational effectiveness. <br />• Watcon system designed at service flow level of 55 gallons per minute. <br />• Watcon system designed at peak flow level of 75 galons per minute. <br />• Watcon has estimated "highest usage level" for the facilities to be in the 40 to 50 <br />gallons per minute range. <br />• Watcon system to include two media tanks designed to operate sequentially. <br />• Watcon system to fit within existing (obsolete) system footprint. <br />• Cut sheet for Watcon system attached. <br />