Laserfiche WebLink
4. Pressure tanks shall include a five (5) year pro-rated warranty, from the date of <br />final acceptance. <br />I. Project Data: <br />Specified Hardness: PPM as CaCO3 460 <br />System Design, GPM Continuous Flow 175 <br />Maximum Pressure Drop Continuous PSI 15 <br />System Design, GPM Peak Flow 250 <br />Maximum Pressure Drop Continuous PSI 25 <br />System Design, Gallons per Day (maximum) 25,000/24Hrs. <br />Softener Capacity (per vessel)grains hardness 600,000 <br />Hours per Day:24 <br />Entering Water Temperature:50 <br />Salt Dosage: Pounds per Cubic Foot 15 <br />J. Electric Wiring: <br />1. Softener supplier shall complete wiring to softener. Include necessary wiring <br />and power for softener controls. <br />PART 3: EXECUTION <br />3.1 INSTALLATION AND COORDINATION <br />A. Verify exact layout requirements, and accessibility requirements for each item of <br />equipment. Make necessary modifications to layout in field, to assure accessibility and <br />clearances. <br />B. All work shall be in accordance with manufacturers’ installation requirements and <br />additional code requirements. <br />C. Maintain adequate service clearance around all equipment, including the work of other <br />trades. <br />D. Provide electrical wiring as required for the installation per the Indiana Electrical Code. <br />END OF SECTION <br />15420 - 4