Laserfiche WebLink
PERMIT BRIEFING MEMO <br />1. Facility Description <br />The St. Joseph Energy Center - Water Treatment Facility's (Water Treatment Facility) <br />engages in the production of process well water which is filtered through a greensand <br />system to remove by precipitation iron and manganese, prior to being pumped to the St. <br />Joseph Energy Center. The process will also precipitate arsenic. <br />2. Discharge description: <br />Discharge is primarily backwash water, though sanitary is also included. The Water <br />Treatment Facility will periodically go into a backwash cycle, which will send backwash <br />water to a settling lagoon. The water is metered prior to discharge into the City of South <br />Bend Sewer System. <br />Estimated average discharge is 32,000 gpd, with an estimated 96,000 maximum gpd. <br />3. Sample Site Description <br />Sample Site Outfall 4 745 is located on the east side of the settling lagoon within the lift <br />station, inside the fence along Walnut Road. <br />4. Wastewater Treatment <br />Wastewater treatment consists of a settling lagoon. <br />5. Classification <br />Based on the City's Industrial Pretreatment Program, The Water Treatment Facility is <br />classified as a Significant Industrial User (SIU) and, because of the facility's discharge of <br />> 50,000 gpd - < 100,000 gpd, it is categorized as a Category B industrial discharger. <br />6. Calculation of Limits <br />Discharge limits are applied from the South Bend Municipal Code directly to The Water <br />Treatment Facility's effluent. Find these limits in Part I (A) (2) of this permit. <br />7. Monitoring Frequency <br />Monitoring frequencies are based on South Bend's US EPA approved industrial <br />Pretreatment Program monitoring requirements. However, more frequent monitoring <br />will be required in the first year of new industrial users. <br />Industrial Operator Certification Requirement <br />Operator Certification Requirement: A -SO. — Industrial Certification requirements are <br />based on the criteria listed in Indiana Administrative Code Title 327-5-22-5 <br />