U�$S r Fffid <br />CVAVUs <br />Classified by <br />Underwriters Laboratories, Inc. <br />to UL 1479 and CANIULC-S115 <br />System No. W-L-7153 <br />ANSI/UL1479 (ASTM E814) <br />F Ratings -1 and 2 Hr (See Item 1) <br />T Rating -1/2 Hr <br />I sm A <br />CAN/ULC S115 <br />F Ratings -1 and 2 Hr (See Item 1) <br />FT Rating -1/2 Hr <br />FH Ratings -1 and 2 Hr (See Item 1) <br />FTH Rating -112 Hr <br />SECTION A -A <br />Wall Assembly — The 1 or 2 hr fire -rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner described <br />in the individual U400, V400 or W400 Series Wall or Partition Design in the UL Fire Resistance Directory and shall include the following <br />construction features: <br />A. Studs — Wall framing shall consist of channel studs. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC. <br />B. Wallboard, Gypsum* — 518 in. (16 mm) thick, 4 ft (122 cm) wide with square or tapered edges. The gypsum board type, thickness, number of <br />layers, fastener type and sheet orientation shall be as specified in the individual Wall and Partition Design in the UL Fire Resistance Directory. <br />Max diam of opening is 24 in. (610 mm). <br />The hourly F and FH Ratings of the firestop system are equal to the hourly fire rating of the wall assembly in which it is installed. <br />IwT7 Reproduced by HILTI, Inc. Courtesy of <br />Underwriters Laboratories, Inc. <br />HIM Firestop Systems November 15, 2017 <br />M <br />Ln <br />ti <br />J <br />Page: 1 of 2 <br />