System No. W-L-1297 <br />ti <br />N <br />r <br />1. Wall Assembly — The 1 or 2 hr fire rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specified in <br />the individual U300, U400, V400 or W400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following <br />construction features. <br />A. Studs — Wall framing shall consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) <br />lumber spaced 16 in. (406 mm) OC. Steel studs to be min 2-1/2 in. (64 mm) wide and spaced max 24 in. (610 mm) OC. <br />B. Gypsum Board* — Nom 5/8 in. (16 mm) thick, 4 ft (1.22 m) wide with square or tapered edges. The gypsum board type, thickness, number of <br />layers, fastener type and sheet orientation shall be as specified in the individual U300, U400, V400 or W400 Series Design in the Fire <br />Resistance Directory. Max diam of opening is 32 in. (813 mm). <br />The hourly F and FH Ratings of the firestop system are equal to the hourly fire rating of the wall assembly in which it is installed. <br />2. Through Penetrant — One metallic pipe, conduit or tubing installed concentrically or eccentrically within the firestop system. Pipe, conduit or tube <br />to be rigidly supported on both sides of wall assembly. The annular space between the pipe, conduit or tube and periphery of the opening shall be <br />min 0 in (0 mm, point contact) to max 2 in. (51 mm) in 2 hr fire rated walls and min 0 in (0 mm, point contact) to max 1 in. (25 mm) in 1 hr fire rated <br />walls. As an option, for through penetrant types 2A, 2B and 2C only in nom diameters not exceeding 4 in. (102 mm), the penetrant can be installed <br />with continuous point contact. The following types and sizes of metallic pipes, conduit or tube may be used: <br />A. Steel Pipe — Nom 30 in. (762 mm) diam (or smaller) Schedule 40 (or heavier) steel pipe. <br />B. Iron Pipe — Nom 30 in. (762 mm) diam (or smaller) cast or ductile iron pipe. <br />C. Conduit — Nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing (EMT) or 6 in. diam steel conduit. <br />D. Copper Tube — Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tube. <br />E. Copper Pipe — Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe. <br />3. Fill, Void or Cavity Material* -Sealant — Min 5/8 in. (16 mm) or 1-1/4 in. (32 mm) thickness of fill material applied within the annulus, flush with <br />both surfaces of wall, for 1 hr and 2 hr fire rated wall assemblies, respectively. A min 1/2 in. (13 mm) diam bead of fill material shall be applied at <br />the pipelwall interface at the point contact and continuous point contact location. <br />HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CP606 Flexible Firestop Sealant <br />* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), <br />respectively. <br />Reproduced by HILTI, Inc. Courtesy of <br />M2= Underwriters Laboratories, Inc. <br />Hilt! Firestop Systems July 07,2020 <br />2of2 <br />