Laserfiche WebLink
3.0 Amps @ 120 VAC 50/60 HZ <br />2.0 Amps @ 240 VAC 50/60 HZ <br />• 16 gauge cold rolled steel with removable locked door with Lexan viewing window <br />Standby Current-130 mA <br />Alarm Current-200 mA <br />• 5 Amps power for NACs, 1/0, and P-Link <br />• 3 Amps per NAC, regulated <br />• 1 Amp per 1/0 circuit, regulated <br />• Battery Charger range 8-55 Ah <br />• Battery Charger voltage 27.3 VDC <br />• P-Link maximum current of 1 Amp <br />32' to 120° (0°C to 49°C) with a maximum humidity of 93% non -condensing. <br />NFPA 12, 12A, 13, 15, 16, 17, 17A, 70, 72, 750, and 2001 <br />ANSI/UL 864 - Local (L), Remote Station (IRS), Central Station (CS), <br />Propriety (PPU), Auxiliary (AUX).Type of Service: Automatic (A), Manual <br />(M), Water flow (WF) Sprinkler Supervisory (SS) Type of Signaling: Digital <br />Alarm Communicator (DAC), March Time (March), Non Coded (NC), Reverse <br />Polarity (Rev Pol), Other Technologies (OT) <br />IBC 2000, 2003, 2006, 2009, 2012 <br />SLC Features <br />The Potter protocol is a digital protocol with a proven design for reliability and noise immunity. The sys- <br />tem does not require special cable or conductors for connection of the Signaling Line Circuit as long as <br />the cable is compliant with NFPA 70 and NFPA 72. The system allows for Class A or Class B installations <br />as well as "T-Taps", with a max wiring distance of 10,000 Ft. <br />SLC Loop Accessories <br />The control panel may be connected with up to 60 addressable devices or modules in any combination. <br />The SLC is not restricted by any special wire requirements and may be wired with any wire that complies <br />with the NEC. <br />Analog Photo Electric Smoke Detector is a smoke detector with a listed obscuration of 1.02 <br />to 3.83 percent per foot. <br />Combination Analog Photo Electric Smoke/Heat Detector — a smoke detector with a listed <br />obscuration of 1.02 to 3.83 percent obscuration and a fixed temperature 135' Fahrenheit <br />heat detector. <br />Analog Fixed Temperature Heat Detector that is selectable from 135°F to 185°F. <br />Addressable Duct Smoke Detector with Form C Relay. <br />Addressable Duct Smoke Detector. <br />6" round base that is mounted to an electrical box and wired for connection of one of the <br />above sensors. <br />4" round base that may be mounted to an electrical box and wired for connection to the <br />above sensors. <br />Isolator base that interrupts a short in a SLC and prevents the short from affecting protected <br />devices on the loop. <br />Addressable Relay Base that contains one relay controlled by the SLC. Relay is rated at <br />rated at 2 amps at 30 VDC or 0.5A at 125VAC. <br />Addressable Sounder Base that contains an addressable sounder module that may be con- <br />figured for local, group and all call. <br />Addressable CO gas detector. <br />Addressable photo electric smoke detector for use in DUCT/DUCTR enclosure. <br />DS1317 Revised: 23-Jul-2020 <br />Page 2 of 6 <br />