Laserfiche WebLink
DISCHARGE NOZZLES <br />Discharge nozzles (4, 6, or 8 ports) are used to uniformly distribute the FK-5-1-12. They are <br />performance tested to ensure that the agent is discharged within 10 seconds and properly dis- <br />persed throughout the protected area. Maximum nozzle height for a protected space is 18 ft 4 <br />in (5588 mm) per tier of nozzles. Additional tiers are required for heights greater than 18 ft 4 in. <br />39' <br />Discharge Nozzle <br />Cut View <br />Discharge Nozzle <br />Top View <br />3?S <br />360' Radial Nozzle (8 Port) <br />180° Sidewall Nozzle (6 Port) <br />90' Corner Nozzle (4 Port) <br />39' <br />[11.89m] <br />N <br />360' Radial Nozzle (8 Port) <br />Arrangement <br />39' <br />180' Sidewall Nozzle (6 Port) <br />Arrangement <br />24' <br />[7.32m] <br />\ <br />33.94' <br />[10.34m] <br />MAXIMUM <br />24' <br />[7.32m] \ <br />/5' \\\ <br />90° Corner Nozzle (4 Port) <br />Arrangement <br />1' [305mm] <br />MAXIMUM <br />1' [305mm] <br />MAXIMUM <br />DS1258 Revised:21-Dec-2023 <br />Page 8 of 10 <br />