Laserfiche WebLink
AMERESCOd5 <br />Green . Clean . Sustainable <br />The net result of the as -built changes and wattage measurements is additional savings for this ECM, since the kWh <br />difference between the existing and new as -built fixtures with measurements is greater than the kWh difference <br />between the existing and new fixtures from the original scope. This is shown in the table below. <br />Note: This analysis of the savings associated with just those fixture types being measured is provided as a proxy for the <br />overall savings for this ECM. Also included in the overall savings numbers shown at the top of Page 18 are any as -built <br />changes for fixture types that were not measured, kW demand sa vings for the entire scope, and the natural gas <br />heating penalty (therms) for the entire scope. <br />Total kWh Consumption and Savings Associated with Measured <br />Fixture Types <br />Existing Fixtures <br />New Fixtures <br />Difference <br />kWh with Rated Watts <br />(Original Scope) <br />452,256 <br />293,518 <br />158,738 <br />kWh with Rated Watts <br />(As -Built Scope) <br />542,847 <br />336,672 <br />206,174 <br />kWh with Measured <br />Watts (As -Built Scope) <br />502,308 <br />304,679 <br />197,629 <br />City of Arvada, Colorado I Project #37213 1 M&V Report — Year 2 1 Page 20 <br />