Lighting Improvements <br />The Energy Savings resulting from the lighting upgrades are the direct result of replacing old, inefficient <br />equipment with newer equipment that consumes less energy to operate and generate an equivalent amount <br />of light. A summary of the lighting improvements is included below, and a full line by line lighting scope can be <br />found in Exhibit G-1 of the Amendment. <br />Interior Lighting Scope - Government Center and Work Release Center <br />• Existing interior 32W linear 4' fluorescent lamps and ballasts were replaced with new 15W LED T8 <br />lamps with internal drivers. <br />• Existing interior 28W linear 4' fluorescent lamps and ballasts were replaced with new 15W LED T8 <br />lamps with internal drivers. <br />• Existing interior 17W linear 2' fluorescent lamps and ballasts were replaced with new 12W LED T8 <br />lamps with internal drivers. <br />• Existing compact fluorescent lamps were replaced with LED. <br />• Existing metal halide lamps were replaced with LED. <br />• Occupancy sensors were installed in noted locations where occupancy sensors did not exist. <br />New T8 LED lamps <br />New LED Lamps <br />Gity of youth Bend .-August 272019 35 11. Measurement &t Veriflcatie�n <br />"Pace content is subject to Confidentiality Restrictions" <br />