Laserfiche WebLink
SERVICES <br />Date: August 9, 2019 <br />RE: South Bend Project Number ii9-o64 <br />315 & 319 W Jefferson Exterior Renovations <br />After a review of the scope of the work and a review at the project site <br />We would like to submit <br />A clarification to our bid for the Division D Electrical Work <br />A- Coordinate work -Yes <br />B- Install 2 CT cabinets- Yes <br />C- Install new 120o amp disconnect- Yes <br />It will be a 120o amp Breaker installed in outdoor service entrance enclosure <br />D-Install 800 amp disconnect — No we feel it violates the intent of the National <br />Electrical Code <br />(2) Panels to be fed on second floor are 1-60o amp and 1-400 amp <br />We will install 2- 40o amp breakers in a outdoor enclosure to feed <br />these panels <br />D- 3 Pipes to 120o amp service -Yes <br />F- New 120o amp fuses- No - <br />We will use a breaker to protect the main service and eliminate the <br />120o amp fuses <br />G- New wire to 120o amp service- Yes <br />H- 2-pipes to 800 amp disconnect- No- 800 amp disconnect is not <br />there <br />1 new pipe will be run from each of 2- new 40o amp disconnecting means <br />on the outside to feed 2 panels on the second floor <br />I -New wire from 800 amp disconnect- No <br />New wire will be run from 2- new 400 amp disconnecting means on <br />the outside to feed 2 the panels on the second floor <br />J-Obtain all necessary permits - Yes <br />Sincerely, <br />Randy Ciesiolka <br />574-274-6653 <br />