Laserfiche WebLink
Emergency Generator Level 1 Inspection <br />(Performed Annually)) <br />A trained technician from your company will perform all of the following points and take <br />corrective action, if any, that needs to be taken. Where applicable and when permitted by the <br />customer, during each visit you will check and/or replace the following: <br />1, <br />Tightness of battery cables. <br />25. <br />Engine cooling water <br />2. <br />Cleanliness of battery <br />connections. <br />cables. <br />26. <br />All rubber hoses for <br />3. <br />Battery electrolyte level. <br />deterioration. <br />4. <br />Battery specific gravity. <br />27. <br />Operation of jacket water <br />5. <br />Battery charging <br />heater. <br />equipment. <br />28. <br />Air cleaner element. <br />6. <br />Generator electrical <br />29. <br />Air cleaner seal. <br />connections <br />30. <br />Fan belt tension. <br />7. <br />Generator slip rings. <br />31. <br />Fan belt condition. <br />8. <br />Generator brushes. <br />32. <br />Visually inspect automatic <br />9. <br />Lubrication of generator <br />transfer switches. <br />bearings. <br />10. <br />Engine control panel <br />connections. <br />Start the Engine/Generator set <br />11. <br />Generator control panel <br />and...... <br />connections. <br />33. <br />Check operation of louvers. <br />12. <br />Control panel indicator <br />34. <br />Check for unusual noises. <br />lights. <br />35. <br />Check for unusual <br />13. <br />Control panel fuses. <br />vibrations. <br />14. <br />Day tank electrical <br />36. <br />Check for oil, fuel, and <br />connections. <br />coolant leaks. <br />15. <br />Day tank piping <br />37. <br />Check operation of water <br />connections. <br />temperature safety. <br />16. <br />Day tank pump and flow <br />38. <br />Check operation of oil <br />systems. <br />pressure safety. <br />17. <br />Radiator core for <br />39. <br />Check operation of over <br />cleanliness. <br />speed safety. <br />18. <br />Filler cap gasket and <br />40. <br />Check operation of <br />sealing surface. <br />crankcase breather. <br />19. <br />Concentration of coolant <br />conditioner. <br />Operate the Engine/Generator set for <br />20. <br />Coolant level. <br />15 minutes and ...... <br />21. <br />Antifreeze protection. <br />41. <br />Record fuel pressure at 0 <br />22. <br />Lube oil level. <br />and 15 minutes. <br />23. <br />Engine electrical <br />42. <br />Record oil pressure at 0 and <br />connections. <br />15 minutes. <br />24. <br />Engine fuel connections. <br />