ORDINANCE NO. 3571
BE IT ORDAIAM by the Common Council of the City of South Bend,
Indiana, that:
Part I. Warm Air Winter Air Conditioning Systems
Article I - Definitions
Section 1. S "Tartu air, winter air conditioning systems, shall consist
of one or more warr_i air heating units within individual housings, or within one
common housing, one or more motor - driven blorrers, smoke or vent pipes, individual
leader pipes or trunk line systems, or both, with necessary control dampers for
warm air and return air lines, automatic controls, registers and intakes; and
other appurtenances, such as air filters, air washers, humidifiers, etc., as may
be required.
Section 2. An individual supply system shall consist of separate
ducts, of round or rectangular cross sections, extending from the heating unit.
Section 3. A trunk line system consists of one or more main ducts
with branches.
Section 4. Return ducts may be individual or trunk lines, or a com-
bination of both.
Section 5. In all cases inhere the term "manual" is used, reference is
made to the then existing latest edition of the Code and -anual For The Design
and Installation of Warm Air, YJinter Air Conditioning Systems, as issued by the
National T`darm Air Heating and Air Conditioning Association, 145 Public Square,
Cleveland 14, Ohio.
Article 2 - Estimating ;seat Doss From
Rooms and Building
Section 1. The heat loss in B.t.u. per hour from each room to be
heated shall be determined in accordance with the approved method given in the
I manual, Section A. These values of heat loss are to be used in determining the
r,
0
required standard sizes of warm air and return air ducts, stacks or risers,
fittings, registers, and return intakes.
Section 2. The total heat loss for the building, in B.t.u. per hour,
is the sum of the room heat losses, and is used in estimating the sizes and
capacities of the furnaces, blowers, filters, etc.
Article 3 - Selection of the Furnace
Section 1. The Heating Plant and its component parts shall be
selected to satisfy the maximum hourly B.t.u. requirements of the building,
in accordance with the method specified in the Manual, Section B.
Section 2. All furnaces shall be rated in accordance with existing
codes and methods, recognized by the National ?:'arm Air Heating and Air Conditioning
Association. Ratings shall include:
(a) Bonnet Capacity, in B.t.u. per hour, and
(b) Register Delivery, in B.t.u, per hour
Article 4 - Selection of Ducts, Registers,
and Intakes
Section 1. The selection of branches, risers, fittings, registers,
intakes, and trunk ducts shall be made in accordance with the standard method,
outlined in the manual, Sections C through G.
Section 2. Insofar as conditions permit, the standard sizes of ducts,
fittings, registers, and intakes, shown in Sections B and F of the .anual shall
be used.
Article 5 - Construction Details
Section 1 - ';':all Stacks (Up to and including 14" in width.)
'"
. all stacks shall be constructed of galvanized iron sheets, 30 gauge or heavier.
If slip joints are used they shall be stripped with asbestos paper. ':'.There stack
hems, boots, or other fittings, either for warm air or return air, go through
first floor, all openings around such fittings shall be filled with asbestos fiber
or other non - combustible insulating material to make this opening dust tight. (See
requirements of Fire Underwriters.)
Section 2 - Headers Tight headers must be installed above all openings
for stackheads and return air intakes. (see requirements of Fire Underwriters.)
- 2 -
Section 3 - Round Pipe. Round pipe shall be constructed of galvanized
iron: up to and including 12 in., not lighter than 30 gauge,
up to and including 24 in., not lighter than 26 gauge.
If slip joints are used, joints shall be stripped with asbestos paper.
Section 4 - Rectangular Duct. Rectangular ducts shall be constructed
of galvanized iron:
up to and including 14 in. wide, not lighter than
28 gauge,
to 36 in. wide, not lighter than 26 gauge,
wider than 36 in., not lighter than 244 gauge.
All duct sections 24 in. or wider, and over 48 in. in length, shall be cross
broke on top and bottom and shall have standing seams or angle iron braces. All
joints shall be S and drive strip, or locked.
IQo warm air duct, round or rectangular, shall come in contact with
masonry malls. Insulate around all warm air ducts through masonry walls with not
less than 1/2 in. of insulation.
It is not the intention of this Section to eliminate the use of other
satisfactory, non - combustible materials in the construction of ducts.
Section 5 - Return Air Liners. Bottoms of all return air joist spaces
shall be lined with smooth, air -tight material. All cross bracing should be
removed and joists properly reinforced.
Section 6 - Insulation of Ducts. All exposed warm air ducts passing
through an unheated room shall be insulated with at least 1/2 in. thickness of
insulation. eructs located in cold attic spaces, or cold exposed basement spaces,
shall be insulated v:ith at least 1 in. thickness of insulation.
Section 7 - Duct Supports. All ducts shall be securely suspended from
adjacent building members. I\fo nails shall be driven through duct or stack vialls,
and no unnecessary holes shall be cut therein.
Section 8 - Volume Dampers. Volume dampers of locking type shall be
placed in each warm air run. These may be placed near the main trunk, or in the
stackhead.
Return air ducts and outside air inlet ducts shall be similarly equipped
v..ith volume dampers.
- 3 -
Article 6 - Control Equipment
Section 1 - Blower Controls. An adjustable automatic fan, or blower,
switch shall be placed in the bonnet of the furnace to start and stop the
blower at predetermined air temperatures. The location of the switch and the
adjustment of the setting shall be made according to the recommendations in the
-U- nual, Section H, unless manufacturer's instructions specify otherwise.
Section 2 - Summer Switch. Unless automatically controlled, a manual
switch for summer operation may be placed in the halL:ay or other accessible
location, but must not be placed where it is liable to be turned by mistake.
This switch shall be wired so that it operates the blower independent of the
bonnet control.
Section 3 - Limit Control. A limit control shall be used in conjunction
with any automatic temperature control, to prevent overheating of the heater
unit. This control shall be so constructed that the temperature of the air in
the bonnet cannot exceed about 200 deg. F. The usual setting is about 175 deg. F.
Section 4 - Coal, Hand -Fired Furnace. In addition to the blower switch
and limit control, a room thermostat shall be used which operates a dapper motor.
Damper motors that have current failure protection are preferred types.
Section 5 - Coal, Stoker-Fired Furnace. In addition to the blower switch
and the limit control, the'controls for a stoker -fired furnace shall consist of a
room thermostat, a relay for operating the stoker motor, a barometric draft
regulator and some form of hold -fire control.
Section 6 -- Oil Fired Furnace. In addition to the blower switch and
limit control, the controls for an oil fired furnace shall consist of a room
thermostat, and an approved ignition control.
Section 7 - Gas Fired Furnace. In addition to the blower switch and
limit control, the controls for a gas fired furnace shall consist of a room
thermostat, and approved gas valve and pilot safety control.
Section 8 - Zone Controls. Zone control equipment consists of 2 or more
room thermostats, operating dampers in warm air ducts leading to various portions,
or zones, of the building. 1 :anufacturer's instructions shall be folled in the
installation zone control equipment.
MJW
Section 9 - Electric Circuit for Heating Equipment Only. The owner shall
furnish a separate electrical circuit of proper voltage and capacity to be run
from the house service to a separate panel. This panel shall be for heating
equipment only.
ART II. - Gravity ,:'arm Air Heating Systems.
Article 1 - Definitions.
Section 1. Gravity warm -air heating systems shall consist of one
or more warm -air furnaces, properly cased, together with necessary parts eonsi§ting
of warm -air leader pipes and fittings, return -air ducts, risers, boxes, fittings,
smokepipe or ventpipe, registers, return =air intakes, and controls.
aection 2. In all cases where the term "manual" is used, reference is
made to the then existing latest edition of the Code and u.anual For the Design
and Installation of Gravity Vlarm Air Heating Systems as issued by the National
Warm Air Heating and Air Conditioning Association, 145 Public Square, Cleveland
14, Ohio.
Article 2 - Estimating Heat Loss
From Rooms and Building.
Section 1. The heat loss in B.t.u. per hour from each room to be
heated shall be determined in accordance with the approved method given in the
Yanual, Section A. These values of heat loss are to be used in determining the
required standard sizes of warm -air and return -air ducts, stacks or risers,
fittings, registers, and return intakes.
Section 2. The total heat loss from the building, in B.t.u. per hour,
is the sum of the room heat losses, and is used to determine the size and capacity
of the furnace required.
Article 3 - Selection of the Furnace
Section 1. The furnace shall be selected to satisfy the maximum hourly
B.t.u. requirements of the building, in accordance with the method specified in
the Akanual, Section B.
Section 2. All furnaces shall be rated in accordance with existing codes
and methods recognized by the National ?"arm Air Heating and Air Conditioning
Association. Ratings shall include both Bonnet Capacity and Register Delivery, in
B.t.u. per hour. Register delivery is based upon a 25 per cent reduction from
the bonnet capacity.
- 5 -
Article 4 - Selection of Ducts,
Registers, and Intakes.
Section 1. The selection of leaders, risers, fittings, registers,
and intakes shall be made in accordance with the standard method outlined in
the Manual, Sections C through F. Insofar as conditions permit, the standard
sizes of ducts, fittings, registers, and intakes shown in Sections E and F of
the 'manual shall be used.
given to.
Article 5 - Installation Details
Section 1. In locating the furnace, due consideration should be
(a) equalizing the length of the leader pipes.
(b) spacing the retarn air ducts equally around the
casing,
(c) minimizing the length of the smokepipe,
(d) ease of firing and servicing the furnace.
Section 2.
(a) Furnace foundation of brick, cement, or other incombustible material
must be provided. Said foundation shall extend at least 15 inches at rear and
sides of furnace casing, and at least 36 inches in front of furnace casing.
Foundation is to be level.
(b) Where it is necessary to place a furnace on a combustible floor,
not less than 5 inches of hollow tile shall be used in every instance, having joints
matched in such a way that air passage will be free from side to side, so that
at no time will the removal of ashes or the handling of coal close up these openings.
Such foundation shall be constructed upon, and covered with continuous sheet metal
plates, of not less than No. 24 gauge metal, having all joints substantially
riveted or double seamed and the bottom sheet to have the edges turned up at least
one inch. This floor covering shall extend under the whole of the firebox and
ashpit of the furnace and outwardly not less than 12 inches on all sides and rear
of casing or base ring and 36 inches in front.
Section 3 - Setting or Assembling of Furnace.
(a) The base ring of any portable -r.arm -air furnace shall be cemented
to the foundation, and cement flushed around the inside of the base rings, making
an air -tight joint. The furnace parts shall be assembled plumb and level and in a
workmanlike manner..
(b) All sections and joints shall be properly fitted. Joints
requiring cement shall be well fitted and all bolts shall be drawn up tightly.
Section . Casings.
(a) warm air furances shall be enclosed in metal casings.
(b) Sheet metal casings, including casing tops or bonnets shall
be made of metal sheets not lighter than 26 U. S. Standard Guage. They shall
fit the castings and casings rings closely, so as to be dust tight and shall be
securely fastened to the front. The casing shall be lined in compliance with
manufacturerts specifications.
(c) ]Rhen side collars are used the casing top or bonnet must be of
sufficient height so that the largest warm air pipe can be taken from side without
availing. In no case shall a distance less than 8 inches be maintained between
the top of the furnace and the bonnet.
(d) Any furance, the casing top of which shall come within 12 inches,
of a combustible floor, ceiling or joist, shall be protected by a metal shield,
extending not less than 18 inches beyond the casing of said furnace. This shield
shall be suspended at least 2 inches below woodwork, allowing free air space
between shield and woodwork. No furnace casing or top, coming nearer than 6 inches
Of ceiling or joists shall be allowed in any case. All metal casing tops shall
be insulated with an air space or covered with magnesia, asbestos boiler covering,
or sand.
(e) Openings for side casing collars shall be cut into the casing top
or bonnet, so that t1ae tops of all openings are on a level. Casing collars shall
be fitted into place with a flange, or bead on the outside and drawn up on the
inside, making a dust -tight joint. All collars shall not be less than the same
size as the warm air pipes to which they are to be connected.
Section 5. Warm Air Pipes in Basement.
(a) All warm air pipes shall be constructed entirely of noncombustible
material equivalent in structural strength and durability to the following:
Diameter 16inimum
Minimum Thickness
Inches ;_'eight of Tin of Galvanized Iron
Less than 12 IC (107 lb.) 30 U. S. guage
12 or more IX (135 lb.) 28 U. S. guage
- 7 -
Y
Side seams shall be locked seams. All joints shall be either seamed or lapped
not less than 12 in. Such joints shall be match- beaded or beaded. All pipes and
fittings shall be properly secured to ceiling or joist.
(b) All warm air pipes in the basement should preferably have an upward
pitch of 1 in. per running foot, but in no case ehould the pitch be downwards
from bonnet to boot.
(c) All warm air pipes, in the basement shall be provided with dampers
supported on both sides and as near the casing as possible.
(d) Nhere warm air pipes pass through a masonry wall a metal thimble
shall be provided, having a diameter at least 1 in. greater than the pipe, and
pipe supported in such a manner that the air space is uniform on all sides. The
air space may be filled with non - combustible insulation.
(e) where warm air pipes pass through or into unheated spaces separated
from the furnace room, they shall be insulated with not less than three layers
of air cell asbestos paper or installed with an equivalent insulating substitute.
(f) All applicable provisions in the Underwriters' Standards shall be
followed. (See Section 310 "warm Air Supply Ducts. ")
Section 6. Wall Stacks or Risers.
(a) warm air risers shall be constructed entirely of non - combustible
material equivalent in structural strength and durability to the following:
Width Minimum Minimum Thickness
Inches ;" ?eight of Tin of Galvanized Iron
14 or less IC (107 lb.) 30 U. S. gauge
over 14 IX (135 lb.) 28 U. S. gauge
(b) All applicable provisions in the Underwriters' Standards shall
be followed. (See Section 310 ":'larm Air supply Ducts" which give provisions for
both single -wall and double -wall construction.)
(c) All risers shall be braced in a proper manner so as not to obstruct
the flow of air but to retain the full capacity throughout.
Section 7 Registers.
(a) When the baseboard or wall registers are used, they shall be
properly sealed to the stack head in such a manner as to prevent any leakage of
air between the head and the register.
MW
(b) Registers for warm air, and warm air pipes, stacks and fittings
shall not be located in outside walls unless properly insulated with 1 in. air
cell covering or its equivalent on the cold side.
(c) For any system having not more than two warm air openings, at
least one of these openings shall be without valve or louvers and the pipe thereto
shall be without, damper.
(d) All applicable provision in the Underwriters' Standards shall be
followed. (See Section 322).
Section S - Return Air Supply to Furnace.
(a) The selction of ducts, risers, fittings and intakes on the
return air side shall be made in accordance with the standard method, outlined
in the Manual, Sections C through G. Returns should be short, dieect, and with
least number of turns and restrictions.
(b) All applicable provisions in the Underwriters' Standards shall be
followed. (See Section 360 entitled "Cold or Return Air Ducts. ")
(c) The air supply to the furnace may be taken from within the building
or may be taken partially from outside and partially from within. All joints in
the duct system shall be made dust tight.
(d) i7here a boot or shoe is connected to the casing at the base, the
opening shall not extend higher than a line on the level of the top of the grate
of the furnace. The width of the shoe shall be of proper measurement to make
the area at all points at least equal to that of the round or square pipe. This
boot or shoe shall be of streamline transition construction.
(e) ITherever the space between joists is used to convey return air
over head, all bridging and bracing shall be removed and a dust proof sheet metal
bottom shall be constructed. If more area is required two or more spaces may be
used, or a pan may be constructed to extend below the joist to obtain the required
area. The connection from this pan to the boot or shoe shall be made of galvanized
iron not lighter than No. 26 U. S. Standard Gauge, and shall have a transition
fitting, the top area of which shall be at least 10 per cent greater than the area
of the connecting pipe. To reduce friction and for the sake of cleanliness, it is
recommended that the joists and all wooden surface between such joists be lined
with metal.
(f) The return -air face, or faces, shall be made of metal. there
return -air face is placed in a seat or side wall (whether furnished by owner,
general contractor, or furnace contractor) the open work of face must extend to
within at least 1 inch of the floor line and not more than 14 in. high.
Section 9 - Smoke Pipes.
(a) The smoke pipe shall be as short and direct as consistent with
the location of the furnace. It shall be made of metal not lighter than No. 24
U. S. Standard Gauge, and not less than the full size of the collar on the furnace
throughout its entire length. It must have no opening for attaching fireplace,
stove, range, water heater, gas or ventilating connection. It shall be lock
seamed or riveted; all joints shall lap not less than lz inches and it shall be
rigidly secured. Cast -iron smoke pipe may be used.
(b) All smoke pipes shall be provided with check dampers, placed on
the side of the pipe or at the end of a tee; when cast -iron smoke pipe dampers
are used they must be placed between the check damper and the furnace and supported
on both sides of the pipe.
(c) Where the smoke pipe enters the flue, a thimble shall be cemented
into the flue and the connections thereto made air tight. Should,any smoke pipe
come within 18 inches of any combustible material, such combustible material must
be covered with asbestos paper and a metal shield so fastened that a 2 inch air
space exists between this shield and the combustible material. This shield shall
be no less in size than twice the diameter of the smoke pipe and of sufficient
length to cover the combustible material at all points.
(d) No smoke pipe shall project through any external wall or window.
No furnace connection is to be made to a flue without a cast iron or steel cleanout
having first been provided in the flue.
Article b - .Pipeless Furnaces.
(a) :then but one duplex grating is used for both warm air and return
air in a so- called pipeless furnace, the area of the return -air intake shall be
at least equal to the area of the warm -air outlet of the grating. Art. 5, Sec. 4,
relative to casings shall not govern when this type of furnace is installed, but
th9 following specifications shall be followed: The inner casing of this type of
- 10 -
furnace may be made of either black or galvanized iron not lighter than No. 26
U. S. S. Guage. The outer casing must be made of galvanized iron not lighter
than No. 26 U. S. S. Guage. A uniform air space shall be maintained at all
points between the inner and outer casing. In no case shall the top of the
heater be allowed closer than 12 inches to any ceiling or joists above the
furnace.
(b) Where joists are cut to accommodate this furnace, headers shall
be put in and braced.
(c) Article No. 4 for determining sizes of warm -air pipe shall not
govern in figuring a pipeless furnace.
(d) There one warm -air register face is used and separate face or
faces for return-air supply are used, then Article No. 5, Section 8 shall apply.
Article 7 - Chimney
The following provisions shall be made by the owner or building
contractor in any building wherein a gravity warm -air heating system is to
be installed. Provide a chimney for the furnace, constructed in a manner to
comply with the following specifications:
(a) The chimney must be absolutely smoke tight throughout its entire
length, and must extend at least 3 feet above a flat roof or 2 feet above the
ridges of peak roofs.
(b) I£ built of a single thickness of brick or of concrete blocks
it shall be lined throughout its entire length with fire -clay lining, having
not less than $/4 inch thickness. Flue linings to be laid in mortar and made
air tight.
(c) The furnace flue must have no other opening for attaching any
fireplace, furnace, stove, range, water heater, gas or ventilating connectioh.
(d) If necessary to effect the flue it must be done in such a manner
as not to reduce the cross sectional area or create a ledge or obstruction, where
loose material may lodge.
(e) Where two or more flues are included in one chimney they must be
completely separated from top to base by masonry partitions not less than 4 inches
thick. Each flue must have a separate cleanout.
- 11 -
(f) Flues may be either round or rectangular. The minimum size shall be
not less than 10 inches round or 821 inches by 13 inches rectangular.
(g) Transite, vitroliner, aluminum or an equal shall be permissable in
lieu of above and shall be compulsory in case of an unlined chimney.
(h) It is strongly recommended that all new chimneys be built in strict
accordance with the ordinance recommended by the National Board of Fire Underwriters,
Article 8 - Building.
(a) Where warm -air register boxes, heads, pipes or stacks are to
be installed, joists shall be set not less than 16 inches on centers and shall
be butted and not lapped. Studding shall be set directly over and under joists,
leaving a space of not less than 14 inches between studs and joists. Wherever
joists are cut, headers must be put in to support joists.
(b) All first story single or sub - floors shall be continuous. In
all houses having studded exterior walls, these floors shall be extende4 o the
outside sheathing and all spaces between studding shall be closed at the attic
line.
(c) It is strongly recommended that the attic be tightly floored or
ceilings insulated to reduce heat losses.
(d) All partition walls (or sections of these walls) in which heat
stacks to second or third floor rooms are to be installed, shall be of sufficient
size to accommodate stacks required to heat said rooms.
PART III. General
Article 1 - Regulations Relating to $safety From Fire
Section 1. Standards relating to reasonable provisions based on
minimum requirements for safety to life and property from fire shall be determined
by reference to any and all provisions of other ord_nances of the City of South
Bend, statutes of the State of Indiana, and shall in any event be the equivalent
or better than the standards of the National Board of Fire Underwriters as contained
in pamphlet No. 90 of said organization published August, 1942, together with
changes, additions and amendments thereto, if any, and any further publications
which may take the place of said pamphlet.
- 12 -
Article 2 - Replacement Installations and
Installations in Old Structures
Section 1. Replacement installations in existing buildings or new
installations in existing buildings under circumstances in which the fulfillment
of the requirements of this ordinance is impossible, or the cost of such fulfill-
ment prohibitive, may be made provided that the inspector assigned to such work
approves plans and specifications therefor in writing, and provided that the
!/ sl gives its written approval thereof.
Article 3 - Sheet Metal ?Mork
Section 1. Except where otherwise provided in this ordinance or in
standards referred to herein and adopted as a part of said ordinance, all sheet
metal work relating to or connected with any of the matters covered by this
ordinance shall be in accordance with the standards set up from time to time
by the Administrative Building.Council of Indiana.
Article 4 - Additional Standards
Section 1. Except as otherwise provided in this code, all installations
included within the code shall be in conformity with the provisions of this ordinance,
the statutes of Indiana, orders, rules and regulations issued by authority thereof
and with approved standards referred to herein. ?there no specific standards are
prescribed by this ordinance by the statutes of the State of Indiana, or by
any orders, rules or regulations issued by authority thereof or in the sets of
standards otherwise referred to in this ordinance, then conformity with the
regulations made and provided by the American Society of Heating and Ventilating
Engineers shall be prima facie evidence of a standard reasonably safe for persons
and property and shall be considered as an approved standard.
PART IV.
Article 1 - Violations
Section 1. Any violation of this ordinance shall subject the person,
firm or corporation guilty of the violation to a fine of not less than Five (5.00)
Dollars, nor more than One Hundred ($100900) Dollars for each such violation.
This ordinance shall be in full force and effect from and after
its passage by the Common Council, its approval by the Mayor and its legal
publication.