HomeMy WebLinkAboutEmergency Quote – Ratify Emergency Replacement of Boiler for Weather Amnesty Building - Edward J. White, Inc.1316 COUNTY -CITY BUILDING I �,�'i PHONE 574/ 235-9251 227 W. JEFFERSON BOULEVARD F FAX 574/ 235-9171 SOIJTH BEND. INDIANA 46601-1930 � CITY OF SOUTH BEND JAMES MUELLER, MAYOR BOARDU IC WORKS January 14, 2020 Mr. Jeffery M. Bucher, Jr, Edward J. White, Inc. 1011 S. Michigan St. South Bend, IN 46601 RE: Emergency Quote Dear Mr. Bucher: The Board of Public Works, at its meeting held on January 14, 2020, approved the above referenced quote to ratify the emergency replacement of the boiler for the Weather Amnesty Building (former Salvation Army Building at 510 S. Main St.) in the amount of $50,219. Enclosed please find a copy of the agreement for your records. If you have any further questions regarding this matter, please call this office at (574) 235- 9251. Sincerely, Linda M. Martin, Clerk Enclosure GARY A. GILOT ELIZABETH A. MARADIK THERESE J. DORAU JORDAN V. GATHERS JOSEPH R. MOLNAR ��� �� ml � ,4ar> � I t J� �Nev �..T. �;� PbimbirT • Reating • Air C'onelitioi)ing ® h'oders Cominerciad • Res'ielential • ///dustrinl December 31, 2019 City of South Bend Attn: Jeff Young 227 W. Jefferson Blvd. South Bend, IN 46601 Re: Old Salvation Army Building Boiler Replacement & Improvements Dear Mr. Young: We are pleased to quote you on the replacement of your existing steam boiler, as well as improvements to the steam boiler system, at the old Salvation Army Building at 510 South Main Street in South Bend, Indiana. The existing steam boiler failed at just over a year old. Based on my walkthrough and our conversations yesterday, it appears that there is an extremely large amount of sediment and debris in the boiler systems condensate return and feed piping. The build-up of this sediment through the years, as well as the migration of this sediment through the system and subsequent lack of treatment to the boiler make-up water, appear to have ultimately contributed to the failure of this boiler. We were not the original installers of this boiler so we cannot speak to the conditions of the system at the time of installation. However, based on the amount of sediment that is being reported and observed, it does not appear that any efforts were made to flush the existing system at the time of installation and no treatment methods were put in place after installation to reduce or eliminate the build-up of this debris. This sediment is caused by the naturally occurring minerals and sediment that is in the municipal water system which is used for the boiler make-up or feed water. When either hard or soft water is used for the make-up (preferably soft water), chemicals are used to neutralize this sediment and then ultimately get rid of it through either manual or automatic blowdowns of the boiler system. Since the amount of sediment is so high and these treatment methods are not currently being employed, what we are proposing is not only the replacement of the boiler, but also the installation of systems and implementation of procedures to highly reduce or eliminate these issues in the future. The following are the proposed means and methods associated with the boiler replacement: • Remove the existing boiler and discard off site. o Due to the amount of sections that are leaking, the cost to replace only the sections (and the amount of labor involved) is as much as ordering a completely new boiler. o Since there will be some overlap on parts, we would save any components that could be used for future repairs and stockpile them off to the side in the boiler room. • Furnish and install one (1) new Weil -McLain Model LGB17S steam boiler. o New boiler is an EXACT replacement to the existing model on site. This eliminates the need for any modifications to the piping, venting, electrical, etc. and also provides for spare components that can be salvaged from the existing boiler. • Reconnect all applicable piping, electrical, venting, controls, etc. to the existing systems. • Provide documented start-up as well as a combustion analysis of the completed boiler installation. 1011 South Michigan Street o South Bend, 1N 46601 t, Phone: (574) 289-6351 • Fax: (574) 289-3755BBB �E www.ejwhiteinc.net /.iceaserf— Rorlded— lnsurcd IA Liccnsc #(_7'810214773 al= • Includes all applicable permits for this wok with St. Joseph County/City of South Bend. • Includes a new warranty on the boiler package. Additional system modifications included to improve system performance and longevity: • Pipe in low -point drains at a few locations on the basement condensate piping, temporarily connect city water to the system and flush the entire lower level condensate main of sediment and debris. • Replace the check valves on the boiler feed piping so that we can ensure they are new and operational. • Furnish and install one (1) Peerless Model 30FME water softener for the make-up water feed to the boiler feed tank. o Includes six (6) bags of salt for the initial fill of the tank and a few extras. • Furnish and install one (1) chemical feed pump with 15-gallon drum of treatment chemicals and initial chemical treatment set-up and service. o We have included the initial chemical feed pump, chemicals and set-up. After the initial set-up, our recommended chemical treatment contractor, Zinkan Chemical, can contract directly with you to perform monthly check-ups and any required chemicals (about $100 per service call plus chemicals). This would only be needed during the heating season while the boiler is in use. o Includes applicable wiring and relays to interlock the chemical feed pump to the boiler feed unit so that treatment chemicals are introduced to the system whenever make-up water is introduced. All work includes: Owner training on the proper operation of the system including explanation of boiler operation, chemical treatment and necessary condensate/boiler feed water blowdowns to remove sediment. All applicable permits for this wok with St. Joseph County/City of South Bend. A one (1) year warranty on all Edward J. White, Inc. furnished and installed material and equipment associated with this project. o The new boiler comes with a one (1) year parts warranty and ten (10) year warranty on the cast iron sections. A copy of the manufacturer's warranty statement is attached to this quotation. We will perform this work for the sum of Fifty Thousand Two Hundred Nineteen and 00/100 Dollars ($50,219.00). Does not include sales tax. A copy of your tax exemption certificate must be on file prior to starting the project. All work performed Monday through Friday between the hours of 7 AM and 3:30 PM EST. Pricing is based on the assumption that the existing freight elevator is operational and can be used to move the old and new sections in and out of the building. The new boiler has a lead time of approximately one (1) week from date of order. If you decide to proceed with this work, please notify our office ASAP so that we can get everything coming. Please contact our office with any questions. Respectfully submitted; Edward J. White, Inc. Jeffrey M. Bucher, Jr. Vice -President °'� f`?" Weil -McLain° Cast Iron Gas Boiler Model LGB Limited Warranty for Commercial Use Please register your purchase of this Weil -McLain Product at www.weil-mclain.com. Retain proof of purchase and installation date. To learn how to properly care for and maintain your Product, please review the printed information provided with your Product. You can also obtain this information at www.weil-mclain.com. A. What Does This Limited Warranty Cover? This Limited Warranty for Commercial Use covers any defects in material and workmanship in your Weil - McLain Cast Iron Gas Boiler Model LGB (the "Product"). B. How Long Does The Coverage Last? There are two separate coverage periods under this Limited Warranty: (1) the Heat Exchanger Limited Warranty Period, and (2) the Parts Limited Warranty Period. The Heat Exchanger Limited Warranty Period runs for ten years from the date your Product was installed. The Parts Limited Warranty Period runs for one year from the date your Product was installed and applies to all parts of your Product except the heat exchanger. Item Coverage Heat Exchanger 10 years All Other Parts 1 year C. Who Can Make Claims Under This Limited Warranty? This Limited Warranty is available to you if you are the original retail purchaser or a subsequent owner and the Product has been used at any time for business purposes. A Product used at all times solely for personal, family, or household purposes is covered by the Limited Warranty for Residential Use for the Weil -McLain Cast Iron Gas Boiler Model LGB. D. What Will Weil -McLain Do To Correct Problems? If Weil -McLain determines during the Heat Exchanger Limited Warranty Period that a heat exchanger section is defective in material or workmanship, then Weil -McLain will provide a replacement heat exchanger section. If Weil -McLain determines during the Parts Limited Warranty Period that any part other than a heat exchanger Page] of 2 section is defective in material or workmanship, then Weil -McLain will provide a replacement part. Weil -McLain will provide replacement heat exchanger sections and other parts free of charge. Weil -McLain will furnish replacement heat exchanger sections from the closest comparable boiler model available from Weil - McLain at the time of the replacement. If Weil -McLain provides a replacement heat exchanger section, then that replacement heat exchanger section will be covered under this Limited Warranty for the time remaining in the original Heat Exchanger Limited Warranty Period. If Weil -McLain provides a replacement for any part other than a heat exchanger section, then that replacement part will be covered under this Limited Warranty for the time remaining in the original Parts Limited Warranty Period. E. What Will Weil -McLain Not Do To Correct Problems? Weil -McLain will not pay for the labor to remove any heat exchanger section or other part that is the subject of your warranty claim or to install replacements provided under this Limited Warranty. Additionally, Weil -McLain will not pay for the cost of any tools, repair materials, or travel necessary to perform the removal or installation. F. What Is Not Covered Under This Limited Warranty? This Limited Warranty does not cover any Product that has been moved from its original installation site and any components that are not supplied by Weil -McLain. Additionally, this Limited Warranty does not cover claims you make if the failure, malfunction, or unsatisfactory performance of, or damage to, your Product resulted from or is attributable to: (1) Inaccurate or incomplete information or data supplied or approved by any party other than Weil -McLain; (2) The failure to properly size the Product for its use; (3) Installation not done in accordance with manufacturer's instructions; 550-141-064 (0314) Weil -McLain® Cast Iron Gas Boiler Model LGB Limited Warranty for Commercial Use (4) Services provided by and workmanship of the installer of the Product; (5) Components that are not supplied by Weil -McLain; (6) Improper or negligent operation, adjustment, control settings, repair, care, or maintenance of the Products, or the failure to adjust, set the controls of, repair, care for, or maintain the Products; (7) Operation with combustion air contaminated by chemical vapors, with improper fuel additives, or with water conditions that have caused deterioration or unusual deposits in the heat exchanger; (8) Freezing, accident, fire, flood, or other acts of God; abuse or misuse; unauthorized alteration; or power surges or failures; and (9) Normal wear and tear. WEIL-McLAIN'S MAXIMUM LIABILITY SHALL NOT EXCEED THE ACTUAL PURCHASE PRICE PAID BY YOU FOR YOUR PRODUCT. IN NO EVENT SHALL WEIL-McLAIN BE RESPONSIBLE FOR INDIRECT, INCIDENTAL, CONSEQUEN- TIAL (INCLUDING WITHOUT LIMITATION DAMAGE TO OR LOSS OF OTHER PROPERTY), OR PUNITIVE DAMAGES, WHETHER SUCH CLAIM OR ACTION 1S BASED ON CONTRACT, WARRANTY, NEGLIGENCE, STRICT LIABIL- ITY, OR ANY OTHER LEGAL THEORY. ALL IMPLIED WARRANTIES, INCLUDING MER- CHANTABILITY AND FITNESS FOR A PARTIC- ULAR PURPOSE, ARE DISCLAIMED IN THEIR ENTIRETY. Page 2 of 2 G. How Do You Make A Warranty Claim? If you believe you have a claim under this Limited Warranty, please contact a qualified heating or plumbing contractor of your choice. Your contractor will perform a diagnosis and advise you as to whether you may have a claim covered by this Limited Warranty. If your contractor advises you that you may have a claim covered by this Limited Warranty, then the contractor will file the claim on your behalf. You must make all parts that are subject to a warranty claim available to your contractor for return to Weil -McLain. if you have questions about this process or the status of your claim, you may call the Weil -McLain Warranty Call Center at 855-627-6003. In addition to the information provided here, you can find complete warranty details and procedures at www.weil- mclain.com. H. How Can You Register Your Purchase? Please register your purchase at www.weil-melain.com. Registration is not required to activate your warranty, but you should retain proof of purchase and installation date. If you have any questions about your coverage under this Limited Warranty, please contact Weil -McLain using the contact information provided above. 550-141-064 (0314) www.weil-mclain.com [111*114`4 COMMERCIAL GAS BOIII ER Series 2 1 Gas I Water or Steam I M[31d: 400...2,860 1 Efficiency 85.1% Net Load Range: [--lot Water 280-2,111 M13H / Steam 975-7,402 Sq. Ft. ADVANTAGESLGB` DESIGN LGBTM sections are made of durable cast iron for long life. It's not uncommon for Weil-McLaW` cast iron boilers to last 3S years or more. Sections are not face ground; the tough outer skin is retained to protect against corrosion. The sections are studded with heat pins that cause the hot gases to swirl about, scrubbing the entire surface for greater heat transfer and maximum operating efficiency. Sealing rope between the sections assures a permanent, gastight seal. When installed, the rope is visible between sections so the boiler can be checked for tightness. Sealing rope — a standard feature of Weil -McLain' commercial boilers — allows for expansion and contraction of the sections, is impervious to heat and moisture, will not crack and will last the life of the boiler. aLLUGING _ I .' � i,,.,. d„, MACHINED Section Seal SURFACE SEALING Modern elastomer sealingu- ..a PING rings in the port openings assure a watertight seal. Because of the elasticity MACHINED of the seals (unlike metal. SURFACE push nipples), theyx " °» fill any gap caused by imperfections in the port openings, misalignment of sections, or expansion and contraction. Combined with short draw rods, sealing rings also permit faster section assembly. Lugs and sockets assure proper section alignment during assembly; the machined surfaces of the port openings control the compression ratio of the rings. Removing the rear jacket panel and steel cleanout plates expose the flue passages for inspection and cleaning. The insulated, galvanized steel base houses the gas manifold and one-piece, high tempurature aluminized steel burners. These burners feature efficient performance, excellent flame characteristics, and quiet ignition and extinction. Burners provide fixed primary air — no adjustment required for approved gases. One burner/base assembly and one gas train are furnished for the LGB1"-4 through 12, and two each for the LGBTI-13 through 23. FEATURES.M.1 ADVANTAGES... BENEFITS re I , ), T I IP , I I , ,,; ,r ; , I I , 1 r I , I, j, A f 0 SYSTEM OPTIONS 01?'TIONAII FIIII� "" CI1I ° RO ' NIII L FOR SNI�)AF[ (AGA) AND CSI�)--1 SYSTEMS I1II° `OR I G IIIBTM 6-23 0 16%.................... _ ry 4� I z r, 1RECESS F ; Ms MOUNTING HOLES STANDARD COMBUSTION CONTROL MNDARID (AGA) AI'MIIN NNCON"T`I�ROL UNIVERSAL CONTROL SYSTEM FEATURES: One Weil -McClain' UCS ignition control module and wire harness are furnished as standard equipment with each base assembly. On a call for heat, the UCS produces a spark to ignite the pilot. When the pilot flame is proven, the main gas valve opens with a built-in, slow opening soft ignition. In the event the pilot is not proven during a timed trial for ignition, the UCS control system will provide 100% shutoff. After a timed 5-minute delay, another ignition sequence will automatically be initiated. The control system has been certified by AGA and all components are UL Listed. The gas train allows for fast and easy installation. A slow - opening, soft ignition, high capacity, combination gas valve is used on the LGBT' 4-5 boilers. T � NIA" ." NII IIII IIII����� � II S � NN � � N°u ° n ' NII"" . N NI'n TIM 6[,' i=m o oNI r�zc)i , S "S I , Illf , IIII IIS WFG FLAME GUARDIAN' CONTROL SYSTEM FEATURES: A pre -wired WFG°' control system consisting of a mounting plate, two Weil -McLain`°' UCS control modules and terminal block are furnished as standard equipment with each base assembly. On a call for heat, the pilot proving control module provides a spark to ignite the pilot. When the pilot flame is proven, the first stage of the two -stage gas valve opens and all burners light on low fire. When the main flame sensor proves carryover, the second stage of the gas valve opens and the burners go to high fire. In the event the pilot or main flame is not proven during a timed trial for ignition, the WFG" control system will provide 100% shutoff. After a timed 5-minute delay, another ignition sequence will automatically be initiated. The control system provides multiple ignition trials. The control system design has been certified by AGA and all components are UL Listed. LOW -HIGH -LOW FIRING: LGB 6-23 boilers can provide low -high -low firing with the addition of a water temperature or steam pressure control. FACTORY-ASSEM BLED GAS TRAIN: The gas train allows for fast and easy installation, A dual gas valve train has an on/off diaphram valve and a low -high -low regulated gas valve. 5 CONTROL ADDITIONAL COMBUSTION Ilumuuun II "' m Il 1-GIB"' — nnutl� II I� ' M" wuu NMm �'dUnim j� II A pre -wired control panel with one ignition control module, a manual reset relay with indicator light and a terminal block are furnished as standard equipment with each base assembly. On a call for heat, the control module produces a spark to ignite the pilot. When the pilot flame is proven, the combination gas valve opens with a built-in, slow opening soft ignition. Upon two consecutive pilot flame failures, the control module will trip the manual reset relay and illuminate the red lockout light. The lockout condition(s) should be corrected before pressing the red reset button to reset the boiler. The control system has been certified by AGA and all components are UL Listed. A pre -wired control panel with one pilot -proving module, one main flame proving module, a manual reset relay with indicator light and a terminal block are furnished as standard equipment with each LGBT" 6-12 boiler. For LGBT" 13- 20, two pre -wired control panels are provided, one for each base. On a call for heat, the pilot -proving module, one main flame proving module, a manual reset relay with indicator light and a terminal block are furnished as standard equipment with each LGBT" 6-12 boilers. For LGBTM 13-20, two pre - wired control panels are provided, one for each base. Upon two consecutive pilot flame failures or on failure to sense main flame, the control module will trip the manual reset relay and illuminate the red lockout light. The lockout conditions) should be corrected before pressing the red reset button to reset the boiler. For LGBTM 13-20, the control systems for each base will operate independently of each other. The control system has been certified by AGA and all components are UL Listed. D I AINDIllf°°°° IIIIcaii,4 rfoi SYS I , wow I , � w 'r1'1 1 AND C ��� I� Illf°°' IIL... IIIISYSTEMS F IIII 1, 2 CONTROL SYSTEM FEATURES: A pre -wired WMBCr" control panel is furnished as standard equipment. The gas train is located outside the boiler jacket. On a call for heat, the pilot control circuit produces a spark and opens t solenoid allowing the pilot to ignite. For LGBT'" 13-23, the universal igniti, produces a spark to ignite the pilot on the second base. After the pilot(! flame safeguard control energizes the main flame circuit allowing the magi uurrrera w iyrIILe dL low fire. The main pilot is then de -energized and the main flame sensor proves the main burner operation at low fire. For LGBT" 13-23, the pilot on the second base continues to burn during the boiler "on" cycle. The flame safeguard control then energizes the downstream gas valve allowing the boiler to fire at high fire. If the pilot or main flame are not proven during the start-up sequence, then the flame safeguard control will lock out on safety. A red indicator light and alarm bell will energize. The lockout condition should be corrected and then the red reset button should be pressed to restart the boiler. The control system will permit a normal start up after an automatic 5-minute delay. The control system has been certified by AGA and all components are UL Listed. 16-gauge panel finished in Weil -McLain blue Hinged front cover (may be removed if necessary) Key lock on front cover Wiring diagrams and operating sequence included in pocket Reset button r1, ��i(til (I<Vrr � I,�tii.drG i1 yh_ i n,�,� �ii(, �;(Jill.roll nni Iii`i,11,r ()v(o4110Ih k vv hn-(r nrrav ennp7 (line(- 1P VrVr1'r� „i''a Jri,(i��t I(r ii n,,, .r(iiiirrV4. in r Ir°, Ample knockouts (top and Fuse protection (spare furnished) Color -coded bottom) to meet any installation 105°C wires I d (one a[ top, two at bottom) 7 Recessed indicator lights and switches for maximum protection Removable Lexan lenses with easily replaced incandescent bulbs — no dimming Light indicates flame failure " Quick -disconnect type connectors Knockout for field application of additional switches Conveniently numbered Wide terminal block tubular screw connectors spacing for ease of wiring rEIR B011 EIRS J I u 1,121; Alternative Piping -for LGBTM-4 through 12 only: If desired, all three piping connections (supply, return and expansion tank) can be taken off same end of boiler. Supply and return sizes in table below for water boilers refer to minimum size of pipe connected to boiler for 20, or higher temperature drop between supply and return. �N AM B0IIII IIII III III° 8 STANDARD, ADDITIONAL AND OPTIONAL EQUIPMENT STANDARD EQUIPMENT, ALL UNITS: m In ">w 'urnc") , rG' r" l y o n I � l' Pdunrlwl/��d STANDARD EQUIPMENT, LG13 Tm-4 and 5: wi-l-lyi �I.r.,ro ciccrl,;,mIc qmrjo STANDARD EQUIPMENT, LGB Tm-6 thru 23: m I kin-w'fII:9r`,? Jrl )iJljcl vollh flmm' okcljolrljc rxy)h'01 r r1i rrr for ljowji —vvo qlmholn :'J]Otol mvin"l jWuq)"fl III I I Y-1 rf o 'InA IIC I )jTf(,,]') l,jln1 4"/:;1 rf I 'fly v Is. d pljoI !I I 'l"r bvi I, och nrJ f n Jd STANDARD EQUIPMENT, WATER BOILERS: cipr wllmp 01,11ji:)l i'� r d ili.l )rf '1I STANDARD EQUIPMENT, STEAM BOILERS: Amq )w'f'Mjj q ccilljol A�:,'Jllj iI: ijol v,flh/�, ;Jdu oiok:i 51 0""'LO 0 ADDITIONAL EQUIPMENT W: 10'-l" ccln:rcl p,'mCk (I !1H, 6 0 \/1'Q1F1'C onvind p'olek lov') vvMi'r l p', Pl); I/llu 0 1 1< I 'd , I Inl! 11 (M4 v) l I S v I Pill.', S v o "A I I Ir, $10 h "(d :)vv :oIMI" 0 ro"i hlqh (i thnl wfl""� 1, 1 a I S l to w le I I,); ;n,),cvsk'm o I ym 1 1 n i re c I i, eiIN,] I 0it cjr r rl rjl,00 h,�,o ��i 'in,jorb WFFP CONTROL PANEL EQUIPMENT STANDARD: vvo )4 vH I "I ll'� 1'floy:: (Ifoill, w \10, Pc lmloj� olo:k " (" rf r, r'l ,i '"A/ 1: 1 t' ) o <"urino l ADDITIONAL: mr)"c' 'Idle Illol' )"d"l h:wll pall ''I WMBCTM CONTROL PANEL EQUIPMENT STANDARD: 0 p�i lcl il 1,11, 11, hirl 2"0 r'10 Pmlcd 'l1IlolI1Ikkm0 p'hI 10 h(%i,ilm icklililomde ijmrol riodukl ) I've v"Ilrucl conlvoi p'wel: )olwalk'qumd p�'[M'IIV/ conkicid cowrol ?lmm Akr)nr) hell LGB"'m DIMENSIONS A sectional length W — Front View Right View li -- 9 56 in 40 2 .7 2 3 N, 5 0 i"13 6" Supply 5 0'1116 421% 2 14 5-"-Rletu-rn Left View We Dimensions (inches) (inc hes) Draft Hood . . ......... " ' - , __ . ............ Outlet(s) M Model A B C W Number & Size MMN . Nil "HMO L LG B T.- 4 18 9 21 1-101, LGBT�_S L 23 11112 26 -12" LGBT%6 28 ..... ... .. 14 — ............ 31 ........... 1-12" LGB--7 1-1-111.11 .... ... ..... .. 33 . . ..... 36 1-12" LGBTM_B ................ 38 19 41 1-14" LGB1.-9 43 211/2 46 1-14" LGB-_10 48 24 ............ 5 ....... ... . 1-16" LGIR'"All 53 261/2 . ............ 56 ........... 1-16" LGBT"-12 58 29 61 1-16" LGBI--13 63 161/2 30 66 2-12" LGB'"-14 68 19 321/2 71 1-12"/ 1-14" LGIBM_15 73 19 . ...... . ..... 35 76 2-14" LGBTm-16 78 211/2 3 7 81 2-14" LGB T M j 2j'v� ... .... . 40 . . . . . . . . . . 86 " LGBTm-1 24 1, � . ................. ........................ 42 . . . . 1 9.... 1-14"/2-14 1-16" LGW"-119 93 24 ---- . ............ 45 .. . — 96 -- , --- 2-1611 LGB'"-20 . ................... -- 98 . . ..... 26Y.... 4T/2__ . ......... 1 oi'-' 2'--16" LGBTm 2 1 103 2 60 106 2 16 LGBT"-22 108 29 521/2 111 2-16" LGBT -23 113 29 55 116 2-16" Motes� (1) ; I (2) CONTROL TAPPING T ABLE Location - Righ roro Size Steam muuu Water ulLeft " El M4 , dtl DI91 C2 1/4 Boiler Drain Boiler Drain Hi. mm.�......., ��������� ... Di & D2 D3 & D4 Yz°` Gauge Glass (3) Left D2 El & , E2 E3 & E4 D Low Water C otf ((( .. � r Optional Low Water Cutoff View Ez M2 El E3 Pressure e O erat� P ng & Limit Controls &Pressure Gauge p Limit Control (2) F1 F2 1 _ To Expansion Tank f or Automatic Air Vent (2) GI G2 3/4 , Operating Control (2) C _ .. H1 & H2 (I) H3.& H4 V J� /," Tncock z M3 D3 E3 Gr ��. J2 2" Steam Relief Valve mm.. Water Relief Valve and Skim H3 k2 ®„Combination & Skim Tapping Tapping Ha K1 K2 /"' .. Pressure & -,D4 '-'E4 Right �...... �. ..__ Temperature Gauge (2) •- . M4 _ ® - �............ . �� � 1 mm -.cz � View M1 & M2 M3 & M4 U"" Optional Low Water Cutoff (;i) Optional Low Water Cutoff MI M3 1 Firing Rate Control (when used) Firing Rate Control (when used) used) � ......., ... ,.,, .................... or Probe Low Water Cutoff I I IMotes„ _ (1) _. (3) (2) ' _ (4U) �... .... Standard AGA CSD 1 & FM IRI Boiler Model mmmm No. of Gas Trains mmmmmm 5" W.C. - 7" W.0 No. of Gas Trains - 5" W.C. �- 7' W.0 No, of Gas Trains .. 5.5" W.C. 7 W.C. LGB 4 �,_ LGB 5 1 ...1 ----- 1 .e,,. 1 ................ ........ ..m .... „..., ,_„ „...�......,� LGB B., 1... Y �.. 9 1 1/ 1�n _. m. 1/ 1"ti LGB7 ,,.... 1 %4 1" 1 1AII - 1 ...................1 1 ...-. 1'/4<" 1° LGB S 1 1/4 0"" 1 1 1 1/ lY" LGB 9 1 P/4 1 1/4I I u 2" 1Y,,, LGB 10 1 1% 1/4 1 1/, 1/4 1 2 1/ LGB 11 ., 1 1�/�, 1 2„ 1�/4„ 1 ................... 2, 1�I,I LGB 12 1 2 1/ 1 2 1/ 1 2` 1/ LGB 13 2 TY4 112 1'A 1 1 2 1 %z" LGB 14 2 4 1/' 4'" 2 s 1114 .. ..m, 1 2 1/2 LGB 15 _ 2 ®� 1 /4 ... 1 2 1'/" -. 8 ,... ..._ 1 2' 11/2„ LGB -16 2 lY 1 2 1/ ... 1 1 2"....... 1/ LGB _17 2 P/4 1 2 1'/4„ 2' LGB 1B 2 ..m,. 1/'/1/4 1/4 /1 2 1/2 /1'/e 1/a /1' 1 2/ . ..1/ LGB 19 2 lY2 P/a" 2 1'/2" ,. , lya° . ... 1 ,. . 2y„ ,,. .,. 2" LGB'm-20 2 1112' / 2 11/4" 2 1/ / 2 2 1 21. / 2 LGB -21 2 2 /0 1 1 �, ... 3 2 1 3 2 ,,, � 2, �,.. P/<" 2 3 2 LGB 23 2,,,,,,,,,,,,,,, ,,, ...... 3 a --- 2" 1 ., 3" 2" it I Assembled Complete AHRI Ce►tified Boiler Approx. Block Packaged Boiler Chimney _ Wet ht Weight Model Model Heatin Input MBH Grof�sBH utp t'ngWate BH�P.r NLbs'hg Size (LDj Numb!l Medium MBH9 Galloens _ Models p ches a LGB-4-W Water 400 322 280 9.7 1 36.5 r 1185 wm 9. 1600 10 ater 520 41 -q 0 1800 12 650 523 455 15 7 54 7 1725 1425 2000 12 LGB-7-W Water ter 780 628 546 m 189 63.9 2005� 1650 2300 12 LGB B W Water 910 737 641 2 0 73.0 2290 1900 250. LGB-9-W Water 1040 843 733 22 5 2 821 2560 2125 G 2800 14 LGB-10-W Water 1170 ___ 950 826 28.3 9112 2800 2375 3100 16 LGB 11 W Water 1300 1057 919 31.5 100.4 3105 .., 2600 3300 16 LGB-12-W Water 1430 1165 1013 34 6 109 5 3365 2650 3500 16 W Water 1560 j!I 1273 1107 „mm 378 1186 3755 31011 0 4100 16 LGB 14 W11 Water 1690 1381 1201 40.9 1277 4085 3330 4300 16 LGB-15-W Water 1820 1459 1295 44.0 136 9 � 4355 ......... ... — 16 LGB 16 W Wa ter 1950 1597 1389 47.2 146,0 4725 17 LGB 17 W Water 2080 1708 1485 50.3 155.1 4975 17 LGB 18-W Water 2210 1817 1580 53.5 164.2 5270 — 18 9 W Water 2340 .. 1926 ,..... 1675 56 6 173 4 5540 ...... .-. .. 18 Water 2470 1770 59 8 182.5 5820 19 LGB 21 W Water 2600 22 7 1919 62 9 191 6 6080 19 LGB 22 W 4 Water 2730 2315 8 2016 661 2012 6365 19 LGB 23 W I Water...... 2860 242 8 2111 69 2 m® 209.8 6625 20 Notes: (1) (2) CS) WM1512_BRO_027 LGB MADE IN THE 12 BOARD OF PUBLIC WORKS AGENDA ITEM REVIEW REQUEST FORM Date Januajj2, 2020� Name David Relos Department DCI BPW Date Januar »�um,awr�rw;r rare. �,...,'�'"'''"''o,m^,�,,.�*re"{�Ssv!w�,r�,v�,�vi�a.mw��,;;a�immoimimmvm✓�� Phone Extension 5836 �r,�,u�amrtmi�omirv�rvmrmr�^��r�r ¢�m�a��.��nn c�mm�muu�iuiuiuiuiuiu�urrm�w.v�r�u�u�uu�w�mvro�ertweaammimmi�� Review and � � ��'oval (c� oarSubmittal �.1...... w �l Prior to Submitt al to Board Diversity Compliance Z� Officer Name �o: _ aa� ..� .....� .w.,�.........� _-- and Inclusion Officer _ Aladean DeRose BPW Attorne y ® Attorney y Name Clara a McDanels Dept. Attorney E] Attorney Name Purchasing ���... .. �� ..... _.m. . .. ...— .�. ........ _ heck the Appropriate Item Tp�,, Pfessional Services A ..e n" . Agreement Contract ro El Open Market Contract Amendment/Addendum E] Bid Opening Bid Award E Quote Opening El Quote Award Proposal Opening ❑ C/O & PCA No. Chg. Order, No., Traffic Control ZwReaI► _erEe Company or Vendor Name New Vendor MBE/WBE Contractor Project Name Project Number Funding Source Account No. Amount Terms of Contract Purpose/Description Information All Submission LJ Proposal Special Purchase, QPA EJ Req. to Advertise Reject Bids/Quotes PCA El Resolution Ease./Encroach ❑ Title Sheel EJ White No ❑ If......- ...� _._ in ...� .. _�....�..... Yes ......_ .� .....�. Yes, Approved by Purchasing ❑ MBE Completed E-Verify Form Attached Yes WBE orme..__SNo r Salvation Army building (510 S. Main St.) _. __. 20JO12 460-36.01 $50,2.1.9 __.,. Emergency replacement of the boiler and related syste ms at the former Salvation Army building at 510 S. Main. For Cliaw8 Orders Only.. .�.� Amount of El Increase $ ....... _ Decrease$ Previous Amount $ Increase /o Current Percent of Change: Decrease ( %) New Amount $ _ _-_ _m_ _..m. ... ... ...�.. .... _ Increase /o TotalPercent of Change: Decrease ��..�...................%) m..................... __....__W.........................................��...__........._....................�..�......� Time Extension Amount: New Completion Date: CITY OF SOUTHBEND COMMUNITY INVESTMENT January 7, 2020 Dear Members of the Board of Public Works, The week end after Christmas, DCI's property inspector Jeff Young checked the former Salvation Army building to make sure it was secure and the mechanicals were functioning properly. He noticed the southern two story section of the building was cold and checked the boiler, which had overheated and was no longer operating. This two story section supplies the one story northern section its water supply and sewer line, so it must be heated. The northern section currently houses the City's Weather Amnesty program, and not having water or sewer service endangers the life and health of the people the Weather Amnesty program serves during the coldest months of the year. Jeff contacted EJ White to inspect the boiler, and it was discovered sediment in the system had clogged valves and overheated the system to the point the entire system needs replaced. Section 14.5-6 of the Municipal Code (the Inclusive Procurement and Contracting ordinance) allows for emergency contracting conditions, defined in Section 14.5-2(q) as "a contract that is awarded on an emergency basis due to a threat of harm to person or property or threat of disruption of government services." Additionally, State law permits emergency contracting without competitive solicitation per IC 5- 22-10-4 and IC 36-1-12-0.1 but requires a memo be submitted to the Board documenting the justifying condition. In consultation with City Legal, having no heat in the part of this building that supplies water and sewer to Weather Amnesty is considered an emergency condition, and we have therefore contracted with EJ White in the amount of $50,219. Two quotes were solicited, with EJ White being the low bid. DAN BUCKEN.MrNTsR AiXEN'NA Ai DRIDGE PAME'LA MEYER UIM C:ORCORAN BusINi,ss DEL VIi01"MENT ENGAGEMENT & ECONOMic Ex[P01VER-,,1VNT NFUGHBORHooD DEVELOPVIF.NP PLANNING EXCELLENCE ACCOUNTABILITY INNOVATION INCLUSION EMPOWERMENT 1400S County -City Building 227 W. Jefferson Blvd, South Bend, Indiana 46601 p 574.235.9371 www.southbendin.gov