HomeMy WebLinkAboutOpening of Bids - Water Treatment Chemicals 2018-2019 - PVS Technologies, Inc.BID/PROPOSAL
CITY OF SOUTH BEND
BID NAME Water Treatment Chemicals 2018-2019
FOR BIDS DUE March 27, 2018 at 9:30 a.m.
Item
No.
Est Qty.
Item
Units
Unit Price
Total
1
150
Chlorine -1 Ton Cylinders
Ton
$ No Bid
$ No Bid
2
150
Chlorine - 150 Lb. Cylinder
Cy'
$ No Bid
$No Baal
3
90,0000
Ferric Chloride
Gal.
$ 1.17
$ 105,300.00
4
260
Fluorisilicic Acid - 23%
Ton
$ No Bid
$ No Bid
5
7,500
Potassium Permanganate - 55 Lb. Pails
Lbs.
$ No Bid
$ No Bid
6
22,500
Blended Phosphate Sequestrant
Lbs.
$ No Bid
$ No Bid
7
25
Solar Salt
Ton
$ No Bid
$ No Bid
8
100
Sulfur Dioxide - 1 Ton Cylinders
Ton
$ No bid
$ No Bid
9
40,000
Dry Polymer Flocculent - 50 / 55 Lb.
Polyethylene Bag
Lbs.
$ No Bid
$ No Bid
10
25,Oo0
Liquid Calcium Nitrate
Gal,
No Bid
$ No Bid
11
30,000
Sodium Hypochlorite - 12.5%
Gal.
$ No Bid
$ No Bid
12
1100
Sodium Permanganate
275 Gallon Totes
Gal.
$ No Bid
$ No Bid
13
1100
Sodium Permanganate
500-500 Gallon Bulk
Gal,
$ No Bid
$ No Bid
14
1100
Struvite Remover 275 Gallon Totes
Gal.
$ No Bid
$ No Bid
TOTAL
$ 105, 300.00
Bidder (Firm)
Address:
PV5 Technologies, Inc.
10900 Harper Avenue
City/State/Zip: Detroit, Mic
an 48213
Telephone Number: 313--571-1100 Fax Number: 313-571-6765
BOARD OF PUBLIC WORKS
Gary A. Gilot, President
Suzanna M. Fritzberg, Member
James A. Mueller, Member
(Printed Name)
Vase President of Sales and Marketing
(Title)
Therese J. Dorau, Member
Elizabeth A. Maradik, Member
Attest: Linda M. Martin, Clerk
CITY OF SOUTH BEND, INDIANA
SELLER'S BID FOR SALE OR LEASE OF MATERIALS
BID NAME Water Treatment Chemicals 2018-2019
FOR BIDS DUE March 27. 2018 at 9:30 AM
Date: March 23, 2018
Bidder
(Firm):
Address: 10900 Harper Avenue
PVS technologies, Inc.
City/State/Zip: Detroit, MI 48213 Telephone Number: 313 571--1100
Agent of Bidder (if Applicable): Craig Mikkelson / PVS Technologies, Inc.
When the prospective Contractor Is unable to certify to any of the statements below, it shall attach an explanation to this Affidavlt.
CONTRACTOR'S NON -COLLUSION AND NON -DEBARMENT AFFIDAVIT,
CERTIFICATION REGARDING INVESTMENT WITH IRAN, EMPLOYMENT
ELIGIBILITY VERIFICATION, NON-DISCRIMINATION COMMITMENT AND
CERTIFICATION OF USE OF UNITED STATES STEEL PRODUCTS OR FOUNDRY
PRODUCTS
(Must be completed for all quotes and bids. Please type or print)
STATE OF Michigan }
) SS:
Wayne COUNTY )
The undersigned Contractor, being duly sworn upon his/her/its oath, affirms under the penalties of perjury
that:
l . Contractor has not, nor has any other member, representative, or agent of the firm,
company, corporation or partnership represented by him, entered into any combination,
collusion or agreement with any person relative to the price to be bid by anyone at such
letting nor to prevent any person from bidding nor to induce anyone to refrain from
bidding, and that this bid is made without reference to any other bid and without any
agreement, understanding or combination with any other person in reference to such
bidding. Contractor further says that no person or persons, firms, or corporation has, have
or will receive directly or indirectly, any rebate, fee, gift, commission or thing of value
on account of such sale; and
2. Contractor certifies by submission of this proposal that neither contractor nor any
of its principals are presently debarred, suspended, proposed for debarment, declared
ineligible, or voluntarily excluded from participation in this transaction by any Federal
department or agency; and
3. Contractor has not, nor has any successor to, nor an affiliate of, Contractor, engaged in
investment activities in Iran.
a. For purposes of this Certification, "Iran" means the government of Iran and any
agency or instrumentality of Iran, or as otherwise defined at Ind. Code § 5-22-16.5-5,
as amended from time -to -time.
b. As provided by Ind. Code § 5-22-16.5-8, as amended from time -to -time, a Contractor
is engaged in investment activities in Iran if either:
Contractor, its successor or its affiliate, provides goods or services of twenty
million dollars ($20,000,000) or more in value in the energy sector of Iran;
or
ii. Contractor, its successor or its affiliate, is a financial institution that extends
twenty million dollars ($20,000,000) or more in credit to another person for
forty-five (45) days or more, if that person will (i) use the credit to provides
goods and services in the energy sector in Iran; and (ii) at the time the
financial institution extends credit, is a person identified on list published by
the Indiana Department of Administration.
4. Contractor does not knowingly employ or contract with an unauthorized alien, nor
retain any employee or contract with a person that the Contractor subsequently learns is
an unauthorized alien. Contractor agrees that he/she/it shall enroll in and verify the work
eligibility status of all of Contractor's newly hired employees through the E-Verify
Program as defined by I.C. 22-5-1.7-3. Contractor's documentation of enrollment and
participation in the E-Verify Program is included and attached as part of this bid/quote;
and
5. Contractor shall require his/her/its subcontractors performing work under this
public contract to certify that the subcontractors do not knowingly employ or contract
with an unauthorized alien, nor retain any employee or contract with a person that the
subcontractor subsequently learns is an unauthorized alien, and that the subcontractor has
enrolled in and is participating in the E-Verify Program. The Contractor agrees to
maintain this certification throughout the term of the contract with the City of South
Bend, and understands that the City may terminate the contract for default if the
Contractor fails to cure a breach of this provision no later than thirty (30) days after being
notified by the City.
b. Persons, partnerships, corporations, associations, or joint venturers awarded a
contract by the City of South Bend through its agencies, boards, or commissions shall not
discriminate against any employee or applicant for employment in the performance of a
City contract with respect to hire, tenure, terms, conditions, or privileges of employment,
or any matter directly or indirectly related to employment because of race, sex, religion,
color, national origin, ancestry, age, gender expression, gender identity, sexual
orientation or disability that does not affect that person's ability to perform the work.
In awarding contracts for the purchase of work, labor, services, supplies, equipment,
materials, or any combination of the foregoing including, but not limited to, public works
contracts awarded under public bidding laws or other contracts in which public bids are
not required by law, the City, its agencies, boards, or commissions may consider the
Contractor's good faith efforts to obtain participation by those Contractors certified by
the State of Indiana as a Minority Business ("MBE") or as a Women's Business
Enterprise ("WBE") as a factor in determining the lowest, responsible, responsive
bidder.
In no event shall persons or entities seeking the award of a City contract be required to
award a subcontract to an MBE/WBE; however, it may not unlawfully discriminate
against said WBE/MBE. A finding of a discriminatory practice by the City's MBEIWBE
Utilization Board shall prohibit that person or entity from being awarded a City contract
for a period of one (1) year from the date of such determination, and such determination
may also be grounds for terminating the contact for which the discriminatory practice or
noncompliance pertains.
7. The undersigned contractor agrees that the following nondiscrimination
commitment shall be made a part of any contract which it may henceforth enter into with
the City of South Bend, Indiana or any of its agencies, boards or commissions.
Contractor agrees not to discriminate against or intimidate any employee or applicant for
employment in the performance of this contract with privileges of employment, or any
matter directly or indirectly related to employment, because of race, religion, color, sex,
gender expression, gender identity, sexual orientation, handicap, national origin or
ancestry. Breach of this provision may be regarded as material breach of contract.
I, the undersigned bidder or agent as contractor on a public works project, understand my
statutory obligations to the use of steel products or foundry products made in the United
States (1.C. 5-16-8-1). 1 hereby certify that I and all subcontractors employed by me for
this project will use steel products or foundry products made in the United States on this
project if awarded. I understand I have an affirmative duty to notify the City in my bid
that my proposal does not include the use of steel products or foundry products made in
the United States. I understand it is my sole obligation and responsibility to provide a
justification to the City, subject to review and approval, why the cost of United States
made steel or foundry products is unreasonable. Prior to award and upon submission of
bid which does not use steel products or foundry products made in the United States, the
City, through its director of public works, shall make a determination if the price of
United States made steel or foundry is unreasonable. I understand that violations
hereunder may result in forfeiture of contractual payments.
I hereby affirm under the penalties of pejjury that the facts and information contained in the foregoing bid
for public works are true and correct.
Dated this 23rd day of March , 20 18
PVS Technologies, Inc.
Signatu—re of Co�lrotractor/Bidder or Its Agent
Craig,Mikk6lson / Vice President of Sales
Printed Name and Title and Marketing
Subscribed and sworn to before the this 23dr day o March
2018
My Corru-nissionExpires- 10/30/2020
N taiw-y Public derry Jones
County of Residence Macomb acting in Wayne
8N)"
OTM
NO AIA Document A31
CONTRACTOR:
(Marne, legal stators and address)
PVS TECHNOLOGIES, INC.
10900 Harper Avenue
Detroit, MI 8213
OWNER:
(.,Vame, legal staters andaddress)
SOUTH BEND
SURETY:
(A'ame, legal status and principol place
of business)
HARTFORD FIRE INSURANCE COMPANY
One Hartford Plaza
Hartford, CT 06155
This document has important legal
consequences. Consultation with
an attorney is encouraged with
respect to its completion or
modification.
227 West Jefferson, South Bond, IN 46604
Any singular reference to
Contractor, Surety, Owner or
BONDAMOUNT: Ten percent of amount bid.
other party shall be considered
0 0'1. of Amount Bid)
plural where applicable.
PROJECT:
(?Vame, location or address, and Project number, ifany)
Furnish and Deliver Ferric Chloride
Project Number, if any:
The Contractor and Surety are bound to the Owner in the amount set forth above, for the payment of which the
Contractor and Surety bind themselves, their heirs, executors, administrators, successors and assigns, jointly mid
severally, as provided herein. The conditions of this Bond are such that if the Owner accepts the bid of the Contractor
within the tirric specified in the bid documents, or within such time period as may be agreed to by the Owner and
Contractor, and the Contractor either (1) enters into a contract with the Owner in accordance with (lie terms of such
bid, and gives such bond or bonds as may be specified in the bidding or Contract Documents, witha surety admitted
in the jurisdiction of the Project and othenvise acceptable to the Owner, for the faithful performance of such Conti -act
and fior the prompt payment of labor and material furnished in the prosecution thereof, or (2) pays to the Owner the
difference, not to exceed the arnourit of this Bond, betNvccn the amount specified in said bid and such larger amount
for w1iich the Owner may in good faith contract with another party to perform the work covered by said bid, then this
obligation shall be null and void, otherivise to remain in full force and effect. '171he Surety hereby waives any notice of
an agreement between the Owner and Contractor to extend the time in which the Owner may accept the bid. Waiver of
notice by the Surety shall riot apply to any extension exceeding sixty (60) days in the aggyregate beyond the time for
acceptance of bids specified in the bid doCUITIents, and the Owner and Contractor shall obtain the Surety's consent for
Carr extension beyond sixty (60) days.
If this Bond is issued in connection with a subcontractor's bid to a Contractor, the term Contractor in this Bond shall
be deemed to be Subcontractor and the term Owner shall be deemed to be Contractor.
When this Bond has been furnished to comply witha statutory or other legal requirement in the location of the Project,
any provision in this Bond conflicting with said statutory or legal requirement shall be deemed r1cleted herefro.kii and
provisions conforming to such statutory or other legal requirement shall be deemed incorporated herein. Wheti so
furnished, the intent is that this Bond shall be construed as a statutory bond and not as a coninion law bond.
Signed a d scaled this 131h day of March, 2018
—PVAHNOLOGIESJVM
A-1 (& a
I k tll-v Sh;qy ne:s
(Title)'Craig , ikkelson / VP of Sales and MArketing
HARTFORD FIRE III SURA,1fNCE COMPANY
(Surqy) -(Seal)
(witness) Samantha Chierici
(Title)
Aerie Walton, Attorney in Fact
AIA Document A3101m — 2010, Copyright 1963, 1970 and 2010 by The American Institute of ArchRects. All rights reserved,
Direct friquiries/Claims to:
THE HARTFORD
POWER
Off"
AT EY
BOND, T-12
One Hartrd Plaza
foectcut
Hartford, Conn06156
Bond,Clalms@ittliartford.com
call: 888-266-3488 or fax: 860-757-5835
Agency Name: AON RISK SERVICES CENTRAL INC
KNOW ALL PERSONS BY THESE PRESENTS THAT: Agency Code: 83-553702
Hartford Fire insurance Company, a corporation duly organized under the laws of the State of Connecticut
Hartford Casualty Insurance, Company, a corporation duly organized under the laws of tile State of Indiana
Hartford Accident and Indemnity Company, a corporation duly organized under the laws of the State of Connecticut
Hartford' Underwriters Insurance Company, a corporation duly organized under the laws of the State of Collnecticut
Twin City Fire Insurance Company, a corporation duly organized under the laws of the State of Indiana
Hartford insurance Company of Illinois, a corporation duly organized under the laws of the State of Illinois
Hartford Insurance Company of the Midwest, a corporation duly organized under tile laws of tile State of Indiana
Hartford insurance Company of the Southeast, a corporation duly organized under the laws of the State of Florida
having their home office in Hartford, Connecticut, (hereinafter collectively referred to as the "Companies") do hereby make,, constitute and appoint,
up to the amount of Unlimited -.
Derek J. Elston, Ann Mullins, Linda M. Napolillo, Christopher P. Troha, Marcia K. Cesafsky,
Jennifer L. Jakaitis, Aerie Walton of CHICAGO, Illinois
their true and lawful Attorneys) -in -Fact, each in their separate capacity if more than one is named above, to sign its name as surety(ies) only as
delineated above by (E, and to execute, seat and acknowledge any and all bonds, undertakings, contracts and other written instruments in the
nature thereof, on behalf of the Companies in their business of guaranteeing the fidelity of persons, guaranteeing the performance of contracts and
executing or guaranteeing bonds and undertakings required or permitted !in any actions or proceedings allowed by law.
In Witness Whereof, and as authorized by a Resolution of the Board of Directors of the Companies on May 6, 2015 the Companies have
caused these presents to be signed by its Senior Vice President and its corporate seals to be hereto affixed, duty attested by its Assistant
Secretary. Further, pursuant to Resolution of the Board of Directors of the Companies, the Companies hereby unambiguously affirm that they are
and will be bound by any mechanically applied signatures applied to this Power of Attorney.
,It Is 14
M
1 )5!,
1-4 'b"O.- #
V. -� �
"Ap
1987 .!Z M
19 7;%
10
��- �-14Z
John Gray, Assistant Secretary M. Ross Fisher, Senior Vice President
STATE OF CON NECTICUT Hartford
COUNTY OF HARTFORD,
On this 1 1th day of January, 2016, before me personally came M. Ross Fisher, to me known, who being by me duly sworn, did depose
and say: that he resides iin the County of Hartford, State of Connecticut; that he is the Senior Vice President of the Companies, the corporations
described! in and which executed the above instrument; that he knows the seals of the said corporations; that the seals affixed to the said
instrument are such corporate seals; that they were so affixed! by authority of the Boards of Directors of said corporations and that he signed his
name thereto by like authority.
�eI74
Nora M.Suanko
Notary Pnbfic
CERTIFICATE My Commission Expires March 31,2018
1, the undersigned, Assistant Vice President of the Companies, DO HEREBY CERTIFY that the above and foregoing is a true and correct
copy of the Power of Attorney executed by said Companies, which is still in full force effective as of Matvg- V�,
Signed and sealed at the City of Hartford.
plits
I0
1979 1�7 9,r)
E)w
Kevin Heckman, Assistant Vice President
POA2016
STATE OF ILLINOIS
COUNTY OF COOK
On this 13"' day of March, 2018, before me, Derek Elston, a Notary Public,
within and for said County and State, personally appeared Aerie Walton to
me personally known to be the Attorney -in -Fact of and for Hartford Fire
Insurance Company and acknowledged that s/he executed the said
instrument as the free act and deed of said Company
IN WITNESS WHEREOF, I have hereunto set my hand and affixed my
official seal, at my office in the aforesaid County, the day and year in this
certificate first above written.
J OF-FICIAL SEAL
DEREK ELSTON
FNOTIARY PUBLIG, G"Off E 0 - ILUNM
c _' k
Notary Public in the State of Illinois my comiviissM EXPWIES 09/0812018
County of Cook
Not Applicable
(To be completed only by Contractors/Bidders claiming to be a local Indiana business" pursuant to I. C. 36-1-12-22)
INDIANA LOCAL BUSINESS PREFERENCE CLAIM
A "local Indiana business" refers to any of the following:
(1) A business whose principal place of business is located in an affected county.
(2) A business that pays a majority of its payroll (in dollar volume) to residents of affected counties,
(3) A business that employs residents of affected counties as a majority of its employees.
(4) A business that makes significant capital investments in the affected counties as defined in rules adopted by the
political subdivision,
(5) A business that has a substantial positive economic impact on the affected counties as defined by criteria in rules
adopted by the political subdivision.
An "affected county" refers to St. Joseph County, Indiana, or the following counties located adjacent to St. Joseph
County: Elkhart County, Marshall County, Starke County and LaPorte County
There are the following price preferences for supplies purchased from a local Indiana business:
• 5% for a purchase expected by the purchasing agency to be less than $50, 000
• 3 % for a purchase expected by the purchasing agency to beat least $50, 000 but less than $100, 000,
• 1 % fora urchase expected by thepurchasing agency to beat least $100,000.
Date:
Pursuant to I.C. 36-1-12-22,
preference for Project
South Bend, St. Joseph County, Indiana,
claims a local Indiana business
(Project # ) located within the City of
Li The location of the principal place of business is
(BSS
Q St. Joseph County, Indiana
0 The following county located adjacent to St. Joseph County, Indiana:
Q The majority of the business's payroll for the 12 months prior to the date of this Bid is to residents of St.
Joseph County, Indiana or the adjacent county noted above.
a The majority of the business's employees for the 12 months prior to the date of this Bid are residents of
St. Joseph County, Indiana, or the adjacent county noted above.
If the business is deemed to be the apparent lowest, responsible, responsive bidder, then it shall provide
supporting documentation for the 12 month period prior to the date of the Bid of (i) the total payroll
amount paid to all employees of the business, and (ii) the total payroll amount paid to employees who are
residents of St. Joseph County and the adjacent county noted above.
WHEN SUPPLYING SUPPORTING PAYROLL RECORDS,
BIDDER SHALL REDACT ALL SOCIAL SECURITY NUMBERS.
Dated this 23rd day of March 20._L8
PVS Aechnologies, Inc.
Con a tor/Bidder (Firm
1
Signature of C tract r/Bidder or Its Agent
Craig Mikkelson / Vice President of Sales and
Printed Name and Title Marketing
1316 COUNTY -CITY BUILDING
227 W.JEFFERSON BOULEVARD
SOUTH BEND, INDIANA 46601-1830
PHONE 574/235-9251
FAX 574/ 235-9171
`rDD 574/ 235-5567
CITY OF SOUTH BEND PETE BUTTIGIEG, MAYOR
BOARD OF PUBLIC WORKS
Date: March 21, 2018
To: All Planholders
From Linda M. Martin, Cleric, Board of Public Works
Subject Addendum Number: 1
Project Na1ne
Project Number:
Water Treatment Chemicals 2018-2019
ACKNOWLEDGEMENT OF RECEIPT OF ADDENDUM
Date Received: March 21. 2018
This addendum is being forwarded to you for the above referenced project.
Please sign below and acknowledge receipt of this Addendum
by faxing this sheet to the Board of Public Works at (574) 235-9171
within 48 hours of receipt. A copy MUST also be included with your
bid package upon submittal.
THIS ADDENDUM MAY AFFECT YOUR BID.
Notes:
The attached documents are hereby added to the Specifications and Contract
Documents and become a part of herein.
Company:
Authorized Si
Date: March 23, Z018
Version 4/2/2015
PROJECT NAME: WATER TREATMENT CHEMICALS 2018-2019
ADDENDUM NO. 1
Date: March 21, 2018
To: All Plan Holders
From: Linda M. Martin, Cleric of the Board of Public Works
The following information is to be added/changed to the contract documents:
To clarify Section 4D of the Instruction to Bidders:
A Bidder who wishes to bid on multiple chemicals may submit one (1) total bid with pricing
listed for each chemical which the Bidder intends to bid on. There is no need for a Bidder
to submit a separate and unique bid for each chemical.
You must acknowledge receipt of this addendum by signing the first page,
returning it via facsimile to (574) 235-9171, and a copy of the first page must be
included with your bid.
--- This addendum consists of a total of 2 pages —
Version 4/2/2015
NOTICE TO BIDDERS
Notice is hereby given that the City of South Bend, Indiana, will receive sealed bids at the Office of the
Board of Public Works, 13th Floor, County -City Building, Room 1316, 227 West Jefferson, South
Bend, Indiana, until the hour of 9:30 AM, Local Time, on March 27, 2018, for the following:
Water Treatment Chemicals 2018-2019
Specifications are available for download by visiting the City of South Bend's web page at
www.southbendin.gov:
x Click on "Business"
x Click on "City Public Bids"
x Click on "Request for Proposals, Vehicles, Equipment and Miscellaneous Bids"
x Click on "Bid/Proposal Interest Form" and register your company to receive updated
information regarding this bid
x Select specification to download
x Print the specification or save it to your computer
There is no charge for the specifications. The specifications are also available for review only during
regular working hours in the Department of Public Works, 1308 County -City Building, South Bend,
Indiana 46601.
Bids received after 9:30AM, Local Time, on March 27, 2018, will be returned unopened.
Bids must be on the City of South Bend Bid/Proposal form provided, which includes a Non -
Debarment Affidavit, Non -Discrimination Commitment form, and a Non -Collusion Affidavit Form.
Certified Check or Bid Bond in the amount of not less than 10% must be submitted with the bid. A
refund of the bid security will be issued upon satisfaction of Bid Award.
The Board reserves the right to reject any or all bids or to accept a full or partial award of the bid
or bids which, in its judgment, will be to the best interests of the City of South Bend. If the Board
elects to award the base bid plus an aiternate(s), the Board will look at the totality of the cost
when determining the lowest, most responsible bid.
The Board may reject any bid that does not conform to these requirements as non -responsive.
The Board reserves the right to reject any or all bids or to accept a full or partial award of the bid or bids
which, in its judgment, will be to the best interest of the City of South Bend.
BOARD OF PUBLIC WORKS
Linda M. Martin, Clerk
Publish two times:
March 2, 2018
March 9, 2018
Ver. 13 — 6101115
SPECIFICATIONS + ACY::I
CITY OF SOUTH BEND
Water Treatment Chemicals 2018-2019
March 27, 2018; 9:30 AM, Local Time
Pursuant to notices given, the undersigned offers bid(s) to the City of South Send in accordance with the
following attachment(s) which specify the class or item number or description, quantity, unit, unit price
BLENDED PHOSPHATE SEQUESTRANT CORROSION INHIBITOR...............................................................................5
CHLORINE SPECIFICATIONS ........ ............. ...... ..... ..... ........... ..... ...... ........................... .......... ............. ............................... ..... I I
DRYPOLYMER FLOCCULENT................................................................................................................................................8
FERRICCHLORIDE..............................................................................................................................2
FLUORISILICICACID................................................................................................................................................................3
LIQUIDCALCIUM NITRATE 66%............................................................................................................................................9
POTASSIUMPERMANGANATE...............................................................................................................................................4
SALTSPECIFICATION................................................................................................................................................................6
SODIUM HYPOCHLORITE 12.5%..........................................................................................................................................10
SODIUM PERMANGANATE.................................................................................._ .............................11
STRUVITE REMOVER/PREVENTATIVE................................................................................................12
SULFURDIOXIDE. ..................................................... ........................................................................ ............. . .......... .............. 7
FOR ALL CHEMICALS
For security Durposes vendors shall confirm via fax a cony of the delivery driver's license, truck and trailer
information alone with the anticipated time of arrival not later than 24 hours Drior to arrival. Failure to do
so will be cause for reLction of material, no billable time will be accepted.
61'ater Yi�orks facility deliveries are to be made on normal work days between 7:00 a.m. and 11:00 a.m. with unloading to be
completed before 1: 00 p.m, YI'aste Water facility deliveries are to be made behveen the hours of 6:00 AM and 4: 00 PM Monday
through Friday.
No stop -off or fuel surcharges allowed; however, demurrage charges will be allowed after 2
hours per stop, All deliveries are F.O.B. Delivery Point.
Awards of this bid will be divisible by product. Awards will be based on the lowest responsive
and responsible bidder per unit prices on the attached schedule.
All prices quoted are to be effective May 1, 2018 through April 30, 2019 (One Year). Prices are
to be firm throughout that period without increases.
Quantities are estimated and not guaranteed, The City reserves the right to exceed the estimate at
the price quoted here in.
I. CHLORINE SPECIFICATIONS
INCLUDE BOTH 150# AND TON CYLINDERS
A. GENERAL
Only containers which currently are authorized by regulation for chlorine,
which have been inspected and reconditioned as described herein, and which
have been tested within the period required by regulations should be filled. It
is illegal to ship chlorine containers that have been filled by or without the
consent of the owner.
2. Due to the volatile nature of this chemical, the chlorine provider must be able
to have one (1) accredited Safety and Handling of Chlorine class per year for
South Bend Personnel,
3. Chlorine quotes should be deposit -free. No cylinder deposit should be
included in the quote.
Boiling Point
-29.29 F (-34.05 C)
Critical Density
35.77 lb./cu. ft.
Critical Pressure
1118.4 psia 76.1 Atmos.)
Critical Temperature
291.20 {144. C)
Critical Volume
0.02796 cu. ft./lb.
Latent Heat of Va orization
123.7 Btu./lb. @Boiling point
Liquid Gas Relationship;
1 volume liquid chlorine = wt. at
457.6 volumes of chlorine, 825 @
standard conditions
Melting Paint
-149.76 F (-100.98 C)
Specific Gravity - Dry Gas
2.482
Specific Gravity — Liquid
1.468 0 ( - 4 C)
B. CHLORINE 150 POUND CYLINDERS
1. Construction
a) All cylinders must be compatible with Chlorine Institute E►nergency Kit "A". All
kit devices must be useable on any cylinder in chlorine service. The maximum
neck ring dianieter that will accommodate an "A"hood is 4-314 inches.
2. Cylinder Types
a) Chlorine cylinders must comply with DOT specs, 3A480, 3AA480, 25, 3, 3BN480
or 3E1800. The regulations permit only one opening in chlorine cylinders -at
the tap far the valve connection.
3. Cylinder Styles
a) Cylinders may be of three styles: footring, bumped bottom, or double bottom.
4. Cylinder Threads
a) The threads in new cylinders are NGT threads 314-14NGT(CI).
5. Chlorine Ton Containers
a) All ton containers must be compatible with Chlorine Institute Emergency Kit "B".
6. Ton Container Types
a) Chlorine ton container types must comply with DOT spec. 106A500X, DOT or
ICC 106A500, 27, BE27.
b) Ton Container Valve and Fuse Plug Opening Threads
c) The threads in new ton containers are 314-14NGT (CI).
7. Valve Protection
a) The cylinder and ton container valves are protected during shipment and storage
by a removable steel valve protective housing or cap. Pressure relief devices
shall not be covered by the housing.
8. Cylinder and Ton Container Capacity
a) In cases where the capacity of a chlorine container is not known, it can be
determined by weighing it empty and again when completely filled with water,
and by multiplying the weight of water at 60°F by 1.25, This is the maTimum
allowable weight of chlorine allowed in the cylinder or ton container.
��IMATO
1. Cylinder Stamping
a) When manufactured,, cylinders are stamped with DOT specification number,
serial number, and owners and/or builders identifying symbols as well as
inspector's official mark and initial test date [DOT Section 173.34(c)] of 49CFR.
2. Ton Container Stamping
a) When manufactured, ton containers are stamped with DOT specification number,
material, serial number, inspector's official mark, name, mark or initials of
company for whose use the tank is made, (or builder's symbol and serial
number), date of test, and water capacity [DOT Section] 79. 300-18]. Tare
weights may be stamped by builder. Changes in stamping must be made in
compliance with DOT Section 173.31(d) or 49CFR.
3. Retest Stamping
a) Retested cylinders [DOT 49 CFR, Section 173.34 (e)(6)] and ton containers
[DOT 49 CFR, Section 173, 31(d)(7)] must be stamped to show date of retest.
For cylinders, the stamp must include the test facility's certification number in a
prescribed pattern. Ton containers do not require the test facility's number on
the container.
4. Tare -Weight Stamping
a) It is recommended that all new chlorine cylinders and ton containers be stamped
with the original tare weight by the container manufacturer.
D. VALVES
1. Cylinders
a) Chlorine cylinders are to have a single chlorine style Ceodeux D174 valve which
is equipped with a fusible metal plug -type relief device. This is a must comply
safety requirement.
2. Ton Container Valves
a) Chlorine ton containers are to have two identical chlorine style Ceodeux D174
valves near the center of one head. This is a must comply safety requirement.
When vertically aligned, the valve in the upper position is used for gas
withdrawal, and the lower one for liquid withdrawal. The standard ton container
valve is identical to the cylinder valve except that it has no fusible metal type
relief device, and the valve seat diameter may be larger than on most cylinder
valves, There are tow sizes of ton container valves: 314 inch NGT and I inch
NGT.
3. Valve Outlet Threads
a) Outlet threads on cylinder and ton containers are special straight threads
(1, 030" - 14NGO-RH-FXT) which conform to connection number CGA 820 and
B20C which utilize a yoke -type connection. These threads are to accommodate
the outlet cap only and are not to be used far chlorine hose connections.
E. PRESSURE RELIEF DEVICES
1. Cylinders
a) The relief device on chlorine cylinders is a fusible metal plug in the cylinder
valve located below the valve seat. The fusible metal is cast into an 'Alloy "B" or
Alloy "A" holder which is screwed into a tapped hole in the valve body. The
fusible plugs are designed to melt between 158 degrees F and 165 degrees F,
2. Ton Containers
a) Ton container valves contain no fusible plugs. The container itself is equipped
with six threaded fusible plugs, three in each head, spaced approximately 120"
apart.
3. Ton Container and Cylinder Inspection, Cleaning, and Reconditioning
a) In addition to the required period retest, it is recommended that each ton
container and cylinder be internally and externally inspected prior to each
filling. This includes all appurtenances, such as valves and fusible plugs.
Criteria for such inspection is outlined in "Cylinder and Ton container
Procedure for Chlorine Packaging, " Chlorine Institute Pamphlet 17, Sections 3,
4, and S.
F. PERIODIC RETESTING AND RE -INSPECTION
1. Cylinder and Ton Containers to be Tested
a) Cylinders (except DOT 3E 1800) and ton containers must be retested at least
once in five years (DOT Section 173.34e and Section 173.31d).
b) Cylinders cannot be filled until they are retested after the five year anniversary
of the month in which it was tested. Ton containers can be filled until the end of
the calendar year during which their five year test is dare.
c) Retests are also required after any reheat treatment, In addition, retest any
container which shows evidence of weakness at any time, or show a 5 percent or
more loss in weight.
2, Test Procedure
a) Cylinders and ton containers are hydrostatically retested by the hydrostatic
expansion method [DOT Section 173.34 (a) and Section 173.31 (d)], If at the
time of requal f cation a container shows a leak or a permanent expansion which
exceeds 10% of the total expansion, it must be condemned.
3. Container Records
a) Records must be kept showing results of the test, Each container must have the
test date plainly and permanently stamped into the metal of one head or the
chime of each task passing the hydrostatic retest,
G, CONDITIONS OF DELIVERY
1. A South Bend Water Works representative shall specify the location for
chlorine cylinder and ton container deliveries.
2. Delivery Locations:
Location
Type of Container
Address
North Station
2,000 lb. Ton Container
830 North Michigan Street
Carriage Hills
150 lb. Cylinder
52290 Shenandoah Drive
Erskine
150 lb, Cylinder
4116 South Fellows Street
South
2,000 lb, Ton Container
3600 South Main Street
Cleveland South
150 lb. Cylinder
4900 Cleveland Road
Cleveland North
150 lb. Cylinder....
4949 Cleveland Road
Waste Water
2,000 lb. Ton Container
3113 Riverside Drive
3. Vendor personnel shall conduct all activities related to the loading and
unloading of cylinders.
4. Ton containers will need to be delivered with a cherry picker.
5. Minimum deliveries are one (1) ton containers and twelve (12) 150#
cylinders,
6. Supplier must be able to guarantee delivery within 3 to 4 calendar days after
order placement
7. Vendor personnel shall not unload any filled cylinders or ton containers prior
to live inspection by South Bend Water Works Personnel.
8. Vendor personnel shall assist South Bend personnel in the visual inspection of
each cylinder or ton container for;
a) External damage or defect
b) Proper installation of valve protection housing or caps
c) Visual inspection of valves and fusible plugs
d) Determination of markings of retest and recertification
9, Motor vehicles used to ship ton containers shall be properly equipped with lift
equipment suitable for handling containers to any point where the container is
to be loaded upon or unloaded from the vehicle.
a) Cylinders containing chlorine shall be securely lashed in an upright position,
loaded into racks securely attached to the motor vehicle, or packed in boxes or
crates of such dimensions as to prevent their overturning.
II. FERRIC CHLORIDE
A. GENERAL
1. Normal concentration percent by Weight; 33-35%
2, Specific Gravity: 0.33
B. DELIVERY
1. Full truck deliveries (4500 gallons) to the Ferric Feed facility Plant located
at; 3113 Riverside Drive, South Bend, IN 46628
III. FLUORISILICIC ACID
A. GENERAL
The Fluorisilicic Acid supplied under these specifications shall be clean and
free of visible suspended matter and shall not contain more than 0.020 percent
of the "heavy metals", mercury, lead, bismuth and copper expressed as lead
(Pb); and shall contain no soluble mineral or organic substances in quantities
capable of a deleterious or injurious effect upon the health of those consuming
water that has been treated properly with fluorsilicic acid.
2. Product to meet the latest AWWA standard for Fluorisilicic Acid (B703).
3. Price is to be based on a 23% solution.
4. Bidders shall quote price per pound.
B. DELIVERY
1. The vendor shall deliver bulk fluoride to the following well locations in the
quantities as specified by a representative of the South Bend Water Works.
2. 23% Fluorisilicic Acid delivered in tank truckloads.
3. Deliveries are estimated at thirteen (13) tank trucks with two to four stop -offs
per 20,000 lb. load.
4. No stop -off or fuel surcharges allowed however, demurrage charges will be
allowed after 2 hours per stop.
5. Suppliers must furnish own unloading hose at least 40 feet in length with
proper couplings to hook onto two male N.P.T., and must blow off hose to
bulk tank at each stop.
6. City will not accept delivery of more than 10% over the order quantity.
7. Delivery Locations:
Location
Bulk Tank
Address
North Station
1600 gallons
830 North Michigan Street
Carriage Hills
0 gallons
52290 Shenandoah Drive
Edison
1350 gallons
2708 Rockne Drive
Erskine
0 gallons
4116 South Fellows Street
South
600 gallons
3600 South Main Street
Cleveland South
1100 gallons
4900 Cleveland Road
Cleveland North
600 gallons
4949 Cleveland Road
Pinhook
900 gallons.
3801 Riverside Drive
Olive
1750 gallons
915 South Olive Street
IV. POTASSIUM PERMANGANATE
A. MATERIAL
1. Free Flowing Grade Potassium Permanganate shall meet the requirements of
AWWA Specification 603-95 and shall be manufactured domestically and
certified suitable for use in public water supply by appropriate state and
federal agencies.
B. DELIVERY
1. The potassium permanganate shall be delivered in 55 pound pails made of 24-
gauge steel or plastic and shall be equipped with a handle.
a) The pails shall remain the property of the South Bend Water Works.
b) The pails shall be unloaded and neatly stacked at the pumping stations.
2. Deliveries will be ordered on an as needed basis with each delivery consisting
of approximately 8 to 16 (55 Lb.) pails.
3. Deliveries must be made within 5 days of placement of the order,
4. Vendor shall deliver pails to the following site:
a) Water Works North Station — 830 North Michigan Street
V. BLENDED PHOSPHATE SE UESTRANT CORROSION INHIBITOR
A. STANDARDS
I . Product shall be a minimum of 85% sodium pyrophosphate.
2. The remaining ingredient(s) shall also be sodium phosphate material(s).
Product must already be listed in the latest National Sanitation Foundation
(NSF) Standard 60 directory.
3. The percent phosphate as PO4 must be disclosed and by Indiana law, be
marked on the outside of the container.
B. TECHNICAL ASSISTANCE
l . The successful vendor giving a quote must also provide on -site technical
assistance to the Authority for an eight hour day per month for the first six
months of product usage.
2. After the first 6 months of on -site technical assistance, the Authority will
request further on -site technical assistance on an as needed basis.
3, The vendor shall provide a per visit cost in their quote for the additional site
visits.
4. Each visit will be one workday (Monday through Friday only), from 7:00 a,m.
to 3:30 p.m. EST.
5. Vendor must submit the name(s) and resume(s) of the technical representative
that will perform the on -site assistance with your quote submittal.
6. The technical representative shall be an employee or certified representative
of the vendor and have a minimum of three years of experience in the
application of blended phosphate sequestering products in municipal water
supply and be available Monday through Friday from 7:00 a.m. to 3:30 p,m.
EST to answer questions which may arise in applying their product.
C. REQUIREMENTS
I . A list of two municipal references within a one hundred mile radius of South
Bend using the product for a minimum of one year.
2, Each reference must include the name of the municipality, the
superintendent's name, and phone number.
3. A one pint sample must be submitted with bid for analysis.
4. During the contract period, additional sampling and analysis will be made.
5. Contract can be nullified if testing indicates unauthorized changes have been
made to product.
6. Samples of product being used by references may also be sampled.
7. Evaluation
a) Sample product analysis
b) Reference interview and possible sample analysis
c) Verification of ingredients.
8. Testing
a) The City reserves the right to submit samples of the polyphosphate product to an
independent laboratory of the City's choice far chemical, biological, and
physical analysis and testing.
b) Any product which, in the City's opinion, contains hazardous or deleterious
substance or fails to comply with these specifications will be disqualified.
c) The cost of this analysis and testing will be incurred by the vendor with the
understanding that a maximum of ten samples per year will be submitted.
d) Guaranteed minimum available phosphate percentage as PO4 is to be Eighty
Percent (80%).
9. Other evaluation:
a) List of data that confirms products effect on (a) copper, (b) sequestration
b) List of data that confirms company' experience in other cities and technical
support.
10. Certified Analysis
a) The supplier shall provide a certified chemical analysis of a polyphosphate
product sample taken from the production facility from which he proposes to
supply the City of South Bend.
b) He shall further certify analysis to be representative of the product he proposes
to provide the City.
11, Performance Requirements
a) When applied at a rate yielding not more than four (4) parts of polyphosphate as
PO4 to each part of iron and manganese, the product shall be capable of holding
iron and manganese in solution far no fewer than five (5) days at seventy (70)
degrees Fahrenheit in the presence of one-half milligram per liter (0.5 mg/1) free
chlorine residual andfor no less than twenty-four (24) hours at 140 degree F.
b) The City reserves the right to run performance tests once a month.
c) Any product which, in the City's opinion, does not meet the specified
performance requirements or fails to comply with the specifications will be
disqualified.
D. COVERAGE
1. These specifications cover blends of phosphate compounds used to stabilize or
sequester soluble iron and manganese in potable water.
E. PHYSICAL FORM
1. Product shall be a granular form. Powdered material will not be accepted.
F. PHYSICAL STANDARDS
I , Phosphate blend shall comply with the following physical requirements:
a) Color, White
b) Solubility: Conipletely miscible in water
c) Percent Phosphate as PO4 Minimum of 80%
d) Physical Form: Granular
G. CHEMICAL STANDARDS
I. Phosphate blend shall contain only NSP approved phosphorous ingredients,
2. No amines or other chelating agents shall be used.
3. Blended phosphate product formulation shall be only sodium salts of
phosphate compounds,
4. No potassium salts shall be used.
5. Impurities in polyphosphate products shall not exceed the following
concentrations:
Arsenic as AS
0.001 m /l
Copper as CU
0.2 mg/1
Heavy Metals (total as Pb)
0.001 mg/l
Iron FE
0.1 m /1
Manganese as MN
< .05 mg/1
Organics as C
None
Silica as SI02
1.0
Zinc as ZN
0.01 mg/1
6. In addition to the above standards, polyphosphate products shall contain no
substance, for which the Indiana Pollution Control Board has established a
limit in potable water, in a concentration exceeding the limit established for
potable water,
MI[G 10[M0 DIM Kv a1
I , Product shall be shipped in 50 pound bags and stored locally.
2. Deliveries are to be made within two to three days of notice.
3. Vender will be required to deliver product weekly or as needed to each well
field in order to maintain specified stock levels.
4. Weekly delivery receipts will be issued.
5. Delivery sites are as follows:
Location
Address
Carriage Hills
52290 Shenandoah Drive
Erskine
4116 South Fellows Street
South
3600 South Main Street
Cleveland South
4900 Cleveland Road
Cleveland North
4949 Cleveland Road
VI. SOLAR SALT SPECIFICATION
1. The salt will be used to prepare a saturated brine solution which will be used
as a chloride source for the on -site hypochlorite generator.
2. Bids will be all inclusive,
3. Solar salt/Purex manufactured by Morton Salt (or equal) shall be supplied in
bulk deliveries and blown into the brine saturator tank using the supplier's
truck -mounted blower.
4. The existing brine saturator tank has the capacity to receive 25-ton bulk
deliveries,
5. Equipment such as hoses with the 4" quick disconnect shall be provided with
salt delivery by the provider,
6. Off-loading truck air pressure shall not exceed 10 p.s.i, for every salt delivery.
B. PRODUCT
1. Salt for sodium hypochlorite generation
2. To ensure proper operation of the on -site hypochlorite generator, solar salt
shall meet or exceed the following quality parameters:
Description
Percent
Maximum/
Minimum
Water Insoluble
0.01 %
maximum
Calcium Nitrate
0.14%
maximum
Magnesium Sulfate
0.02%
maximum
Magnesium Chloride
0.1 %
maximum
Sodium Chloride
99.82%
minimum
NaCl Wet
93.3%
minimum
NaCl Dry
963%
minimum
Moisture (as H20)
3%
maximum
Lead
0.0007%
maximum
Copper
0.0003%
maximum
Iron (as Fe)
0.002%
maximum
Fluoride
0.01 %
maximum
3. Sodium Chloride content shall be determined per the AWWA B200-03
standard or per ASTM Standard Methods,
4. Salt shall be certified to ANSI/NSF Standard 60 when the sodium
hypochlorite solution produced by the electrolytic generator will be used for
disinfection of drinking water.
5. Salt shall contain no anti -caking or free -flowing additives or conditioners.
6, Salt shall be medium, coarse or extra coarse grade with a minimum bulk
density of 60 lb/ft3 to avoid use of gravel bed in brine saturator tank.
C. PHYSICAL PROPERTIES
1. Purex or Equal
a) The pour (loose) bulk density shall be 1,15-1,25 g/ml (72-78 lbs/ft').
b) Production shall be unscreened, receiving a coarse scalping of 10-14mesh. The
paean crystal size shall be 290-430 ann.
c) The mean surface area of the crystals shall be 65-98 can. sq/g.
d) Sodium Chloride content shall be determined per the AWWA B200-03 standard
or per ASTM Standard Methods.
e) Morton's Purex or equal shall be certified to ANSI/NSF Standard 60 when the
sodium hypochlorite solution produced by the electrolytic generator will be used
for disinfection of drinking water.
f) Morton 's Purex or equal shall contain no anti -caking or free flowing additives
or conditioners.
1. Olive GAC Building, 915 S. Olive Street, South Bend, IN
VII. SULFUR DIOXIDE
A. PROPERTIES
Boiling Point
-10°C
Color
Colorless
Specific Gravity
(80°F)
1.363
Critical Temp.
314.82°F
Critical Pressure
1141.5 PSIA
B. USAGE
Estimated annual usage is 100 tons, more or less, to be delivered in 2,000 lb
containers of liquid SO2 in truckload lots of 10 containers.
C. DELIVERY
1. Supplier must be able to guarantee delivery of 10 tons (20,000 lbs) within five
(5) calendar days from release of requirement.
2, Material to be delivered F,O.B.
3. No freight surcharges allowed,
4. Billing must be submitted on a CWT unit basis.
5, Delivery Location; Waste Water Treatment Plant located at 3113 Riverside
Drive, South Bend, Indiana 46628.
VIII. DRY POLYMER FLOCCULENT
A. GENERAL
1. The purpose of this specification is to outline minimum acceptable properties
of a polymer at the Bureau of Waste Water in the treatment process.
2. Quantity of the polymer stated in this specification is intended as an estimated
usage during a 12 month period rather than an absolute quantity.
3. Polymer is considered a performance product and must meet certain standards
due to compliance related issues on the NPDES Permit.
4. Any supplier that has not been previously approved must perform bench
testing on any polymer bid to prove the product will meet the standards
necessary to ensure permit compliance.
5. When samples are required, such samples shall be delivered or shipped at the
vendor's expense to the following name and address: Nancy Clay, 3113
Riverside Dr. South Bend, IN 46628.
6. Samples must be clearly labeled with your company's name, address, and
(item number).
7. All samples must be representative of the item bid.
8. All samples will become the property of the City of South Bend, and will not
be returned.
B. PROPERTIES
1. Products will be a high molecular weight cationic polyelectrolyte, supplied as
a micro -bead or in granular form.
2. The product must be completely non -dusting, free flowing and completely
soluble in water with a very rapid dissolving rate.
3. Typical Properties
Bulk Density
50 lbs. per cubic ft.
Particle Size
95% less than 1 mm
pH of 1 % Solution
3.5 — 4.5
C. PACKAGING/DELIVERY
1. Packaging to be in 50 -- 55 lb polyethylene bags.
2. Must be able to guarantee delivery of 9,000 lbs within 14 calendar days after
order placement.
3. Prices must be submitted in cost per pound with freight included.
4. Material to be delivered F.O.B. the Waste Water Treatment plant located at
3113 Riverside Drive, South Bend, IN. 46628.
IX. LIQUID CALCIUM NITRATE 66%
A. GENERAL
1. The estimated annual usage of Liquid Calcium Nitrate (66%) is 45,000
gallons, more or less.
2. Supplier must be able to guarantee delivery of 4,000 to 5,200 gallons within
five (5) calendar days after order placement,
B. TYPICAL PROPERTIES
Concentrations:
Ca(NO3)2
46.34%
Ca(NO3)2 0 4H20
66.5%
Ca
11.2%
Mn ( m)
Less than 1
Specific Gravity:
1.454 g/ml at 20°C
pH:
16,00 at 20°C
C. DELIVERY
1. Full truck load quantities are to be approximately 3,500 gallons
2. Delivery will be to two separate remote locations. Geyer Ditch GPS location
41.69565,-86.40614, Sage Road GPS location 41.71024,-86.41629.
3. Remote locations are accessed via a combination lock. Delivery requests will
include the combination lock if City personnel will not be on -site during
deliveries. If City personnel will be on -site the combination will be omitted
from the manifest.
4. Prices must be submitted in cost per gallon with freight included.
r
X. SODIUM HYPOCHLORITE 12.5%
A. GENERAL
1. The estimated annual usage of Sodium Hypochlorite is 30,000 gallons, more or less.
2. The City owns multiple 2,550+ gallon tanks for the storage of Sodium Hypochlorite 12.5%.
3. These tanks come equipped with all necessary fittings and outlets, as well as secondary
containment for increased safety.
4. Supplier must have necessary hoses and connectors to connect to a 2 inch quick disconnect
fitting.
5. Product delivered to a Water Filtration Facility must meet the required ANSIINSF Standard
60.
B. TYPICAL PROPERTIES
Concentrations
Sodium Hypochlorite
12.5%
Specific Gravity
1.1964
PH
12.5 to 13.5
Molecular Weight
74.44
Boiling Point
>212°F
Freezing Point
-11 °F
C. DELIVERY
l . Supplier must be able to guarantee delivery of 1,800 to 4,500 gallons within 3 to 4 calendar
days after order placement.
2. Full truck load quantities of approximately 1,800 to 4,500 gallons are to be delivered, F.O.B.
to:
a) Waste Water Treatment Plant, 3113 Riverside Drive, South Bend, IN. 466.28.
b.) Pinhook Filtration Plant, 2801 Riverside Drive, South Bend, IN 46628.
c.) Edison Filtration Plant, 2708 Rockne Drive, South Bend, IN 46615.
3.) Prices must be submitted in cost per gallon with freight included.
XI. SODIUM PERMANGANATE
A. GENERAL:
1. The bid will be for two separate line items for the same product (20% Liquid Sodium
Permanganate)
2. One line item will be for deliveries of 275-gallon totes.
3. The other will be for deliveries between 500 and 550 gallon increments.
B. TYPICAL PROPERTIES
1. Product shall be bulk 20% (by weight) +/- 0.5% liquid sodium permanganate (NaMn04).
2. 20% Liquid Sodium Permanganate shall be produced domestically with in the United
States.
3. Product shall meet or exceed ANSI/AWWA standard B603-03 or subsequent revisions.
4. Product shall be listed by the NSF as being in full compliance with NSF Standard No. 60
for Drinking Water Treatment Chemicals — Health Effects.
C. DELIVERY
1. All deliveries shall be made within 48 hours of the request to the following address: 2801
Riverside Drive, South Bend IN 46628.
2. The product is to be delivered in clean containers/tanks and is free of contamination.
Contamination of stock shall render the contractor liable for disposal of contaminated material,
cleanup of storage facilities and full replacement of stock at the Supplier's expense.
3. All deliveries shall be made on weekdays (excluding holidays) between the hours 7:00 AM
and 11:00 AM
4. The off-loading of the 275-gallon totes containing sodium permanganate from the delivery
vehicle to the City's storage location will be performed by pressurizing the container to our
point of delivery or by transfer pump.
5. Deliveries must be coordinated with the City. The Identity of the driver must be made known
by fax or email 24 hr. prior to delivery. The delivery vehicle operator must call the City contact
no less than one hour prior to delivery.
6. The Contractor and shipper shall be responsible for all health, safety, and costs associated
with the transportation of the product to the Pinhook WTP. 2801 Riverside Drive 46628.
7. The City reserves the right to reject any delivery which does not conform to these
specifications or which has been contaminated.
r
XII. STRUVITE REMOVER AND PREVENTATIVE
A. GENERAL
1. The purpose of this specification is to outline minimum acceptable properties of a struvite
remover/preventative at the Bureau of Waste Water in the treatment process.
2. Quantity of the product stated in this specification is intended as an estimated usage during a
12 month period rather than an absolute quantity.
B. PROPERTIES
1. The product must be non -toxic and require no additional PPE to handle and/or maintain.
2. Vendor shall supply (at no charge) and maintain (at no charge) all chemical feed pumps,
spray bars, spray nozzles and injection equipment (where applicable).
3. Product must have a minimum dilution rate of 40,000:1.
4. Vendor must have a minimum of five (5) installations with five (5) years of proven process
application of struvite removal and prevention.
5. Product must be manufactured and distributed solely from the U.S.A.
6. Typical Properties
Flammability
None
H
Neutral
Solubility
Miscible
C. PACKAGING/DELIVERY
I. Packaging to be in 275 gallon totes.
2. Must be able to guarantee delivery of 275 gallons within 10 calendar days after order
placement.
3. Material to be delivered F.O.B. the Waste Water Treatment plant located at 3113 Riverside
Drive, South Bend, IN. 46628.
FACP
CITY OF SOUTH BEND' , ri"
INSTRUCTIONS TO BIDDERS
BID FORMS AND EXECUTION
A. Bidders are expected to examine the Drawings, Specifications, Proposal and all Instructions.
Failure to do so will be at the Bidder's risk.
B. Each Bidder shall furnish all information required by the Notice, Instructions to Bidders and
Specifications. Bids must be made on the form provided. The Bidder shall sign the Proposal
and Non -Collusion Affidavit, which is a part of the provided form, where indicated, provide a
notary signature and provide all other information required.
C. The Bidder shall sign the Proposal in the following manner: If the Proposal is made by an
individual, his/her name and post office address must be shown. If made by a partnership or
joint venture, the name and post office address of each member of the partnership or joint
venture must be shown. If made by a corporation, the Proposal must be signed by an officer
of the corporation or by a representative duly authorized by the corporation to execute the
Proposal in its behalf.
2. SEALED BIDS ONLY
A. Bids, Proposals, Guaranty, and other required documents must be submitted in a sealed
envelope marked on the outside with the general classification of material bids, i.e. "Bid for
Computer Equipment," "Bid for Front End Loader," or "Bid for Office Supplies."
B. When samples are required, such samples shall be delivered or shipped at the bidder's
expense to the address specified in the Invitation to Bid. Samples must be shipped
separately from bid documents and labeled clearly with the Bidder's name, address and the
commodity or equipment classifications and documents, the item (and item number, if any),
and Material Safety Data Sheets (if applicable). All samples must be representative of the
commodities or equipment which will be supplied by the successful Bidder. All samples will
become the property of the City of South Bend and none will be returned, unless otherwise
stated in the Specifications.
C. In the event of an inconsistency between provisions of the contract documents, the
inconsistency shall be resolved by giving precedence in the following order:
3. ORDER OF PRECEDENCE
A. Bid Form attached Proposal
B. Amendments to Specifications
C. Specifications
D. Special Provision
E. Instructions to Bidders
F. Notice to Bidders
DELIVERY OF BIDS
A. Bids must be delivered to the Office of the Board of Public Works, 131h Floor, County -City
Building, Room 1316, 227 West Jefferson Boulevard, South Bend, Indiana 46601 (574) 235-
9251, by the time specified (local time) in the Notice to Bidders. If not delivered personally,
the sealed envelope containing the Bid must be mailed to the following address:
City of South Bend
Clerk of the Board of Public Works
1316 County -City Building
227 West Jefferson Boulevard
South Bend, Indiana 46601
B. The Post Office Department will be considered agent of the Bidder in delivering the bid. The
City will not be responsible for deliveries. Any Bids received after the time specified will
be returned unopened.
C. Bids will be opened and read publicly at the time and place designated in the Notice to
Bidders. Bidders, their authorized agents, and the public are invited to be present.
D. Bidders may bid on one (1) or more item, provided however, that the bid submitted for each is
delivered in a separate, sealed envelope, with the envelope clearly labeled on the outside
as to the specific item for which the bid is being submitted. Bidders may submit separate bid
bonds for each item being bid upon OR may submit one (1) bid bond equal to 10% of the
combined total of all bids submitted,
E. The Board may reject any bid that does not conform to these requirements as non-
responsive.
ADDENDA — NO VERBAL INTERPRETATIONS
A. No inquiries by Bidders relative to interpretation of Plans, Specifications, Special Provisions,
or other Bidding Documents will be answered verbally. If any prospective Bidder is unable or
unwilling to comply with one or more requirements of the bidding document, such Bidder
should so inform the Board of Public Works in writing. Upon receipt of such information,
consideration will be given to the advisability of issuing an Addendum which would thereupon
become applicable to all Bidders. Any such inquiry must be submitted at least seven (7) days
prior to the bid opening date in order to give the Board sufficient time to consider any
necessary Addendum. All answers to such inquiries, in the form of Addenda, will be furnished
to all prospective Bidders who have registered with the City. All Bidders are required to
acknowledge receipt of any Addenda by inserting the Addendum number and the issuing date
on executed Proposals.
6. REJECTION OF PROPOSALS CONTAINING ALTERATION ERASURES INCOMPLETE
BIDS AND ETC.
A. Proposals shall be rejected if they show any alteration of form, additions not called for,
conditional or alternate bids (except when and insofar as are invited), incomplete bids,
erasures or irregularities of any kinds.
B. All blank spaces for bid prices must be filled in, in ink, with the unit price and total price for
each item (This does not apply to divisible bids). In case of incorrect totaling of amounts and
where the unit price and the extension thereof do not agree, the unit price for each item shall
govern, and the City is authorized to correct all erroneous extension and totals for the purpose
of comparing bids.
TRADE DISCOUNTS
A. Trade discounts shall not be shown separately, but shall be incorporated in the Bidder's unit
price, unless otherwise specified.
8. VEHICLE BIDS
A. Bidders may bid on one (1) or more vehicles, provided however, that the bid submitted for
each vehicle is delivered in a separate, sealed envelope, by vehicle, with the envelope clearly
labeled on Bidders may bid on one (1) or more vehicles, provided however, that the bid
submitted for each vehicle is delivered in a separate, sealed envelope, by vehicle, with the
envelope clearly labeled on the outside as to the specific vehicle for which the bid is being
submitted. Bidders may submit separate bid bonds for each vehicle being bid upon OR may
submit one (1) bid bond equal to 10% of the combined total of all vehicle bids submitted.
9. The Board may reject any bid that does not conform to these requirements as non-
responsive.
10. TAX EXEMPTIONS
A. The City of South Bend is exempt from the payment of federal excise and transportation taxes
levied under the provision of the Internal Revenue Code. It is also exempt from the Indiana
State Gross Retail Tax (sales tax). The City will furnish the successful Bidder with any
certificate of exemption required.
11. WITHDRAWAL OF BIDS
A. Withdrawal of bids will be allowed only in those cases in which a written request to withdraw a
bid is received by the Board of Public Works prior to the date and hour for receiving and
opening bids. In such cases, the same will be returned to Bidder unopened.
12. ESCALATOR OR CONTINGENT CLAUSES
A. The use of escalator clauses or other contingent clauses by the Bidder is prohibited, unless
requested or permitted by the Invitation to Bid. No Proposal shall contain nor be
accompanied by any writing purporting to limit or qualify the City's right to accept such
Proposal or purporting to alter such Proposal or any Contract which may be executed
pursuant thereto.
13. PRICES MUST BE DELIVERED PRICES
A. The bid price shall be a delivered price. All materials shall be shipped F.O.B. destination as
specified in the Invitation to Bid. No fuel surcharges accepted.
14. AWARD — WAIVER OF TECHNICALITIES
A. The Award of Bid, if any award be made, will be made within sixty (fig) calendar days after the
opening of Proposals to the lowest responsible and responsive Bidder who's Proposal
complies with all the requirements prescribed, exclusive of technicalities waived. Until the
final award of the Bid, however, the right is reserved by the City to reject any and all
Proposals and to waive technical errors.
15. SPLITTING OF AWARDSIDIVISIBLE BIDS
A. Bids will be awarded on the basis of the total dollar amount for all items in the Proposal unless
the bid is described by the City as a Divisible Bid, The City may award a Divisible Bid to the
lowest responsible and responsive Bidder for each item or class of items as indicated in the
bid documents,
16. BIDDER QUALIFICATION
A. The City may require any Bidder to submit evidence of qualifications, and may consider any
evidence of the financial, technical, and other qualifications and abilities of the Bidder. The
City will not award a Contract to a Bidder who, in its opinion, is not fully qualified on the basis
of financial resources and responsibility, possession of adequate equipment, personnel,
experience, and past record of performance to perform the obligations to be undertaken
competently and without delay.
17. PURCHASE ORDERS
A. A Purchase Order will be issued to the successful Bidder after formal acceptance of the bid is
made by the City.
18. NEW MANUFACTURE
A. Unless otherwise specified in the Invitation to Bid, the items offered shall all be new and the
latest model of manufacture.
19. SOURCE OF SUPPLY
A. If the Bidder is not a manufacturer, the source of supply must be shown and all sub-
contractors must be identified.
20. PACKAGING
A. All items shall be delivered strongly packed and marked according to accepted commercial
practice unless otherwise directed in the Specifications. No charge shall be made for
containers and the City shall have no obligation to return containers unless otherwise
provided by the Specifications or Special Provisions. Any items not received in good
condition will be rejected.
21. INSPECTION OF GOODS
A. The City of South Bend reserves the right to inspect and have any goods tested after delivery
for compliance with the specifications. Notice of latent defects, which would make the item
unfit for the purposes for which they are required, may be given at any time within one year
after discovery of the defects.
B. All items rejected must be removed immediately by the Contractor at the expense of the
Contractor. If the Contractor fails or refuses to remove the rejected items, they may be sold
by the City of South Bend.
C. The above provision shall not be construed in limitations of any rights the City may have
under any laws including the Uniform Commercial Code.
22, ASSIGNMENTS
A. No person to whom a Contract has been awarded may assign his interest in the Contract
without the consent, in writing, of the City.
23, CANCELLATION
A. The City of South Bend reserves the right to cancel any Contract for failure or refusal of
performance, fraud, deceit, misrepresentation, collusion, conspiracy, or any other misconduct
on the part of the Contractor.
24. DEDUCTION OF DAMAGES
A. If the City cancels the contract for any cause, it shall deduct from whatever is owed the
Contractor on the Contract or any other Contract, any amount sufficient to compensate the
City for any damages suffered by it because of the Contractor's wrongdoing.
25, METHOD OF INVOICING FOR PAYMENT
A. Contractor shall bill the City of South Bend
1. On regular invoice form giving a complete and detailed description of the goods delivered,
including purchase order number.
2. If the Contractor allows a discount, the period of time in which the City must make
payment to qualify for the discounts shall be computed from the date the City received the
invoice (completely filled out), or the date the goods are delivered and accepted,
whichever may be later, and shall not be less than twenty (20) days.
3. If more than one shipment is made under the Contract and on the same purchase order,
the City will make partial payments on a basis that is agreeable to both parties.
26. OWNERSHIP OF GOODS
A. The goods which are the subject of the Contract shall remain property of the Contractor until
delivered to and accepted by the City of South Bend,
27. ESTIMATED QUANTITIES
A. If the quantity set forth in the Notice to Bidders and Proposal is approximate and represents
the estimated requirements of the City for a specified period of time, the unit price and the
extended total price thereof shall be used only as a basis for the evaluation of bids. The
actual quantities necessary may be more or less than the estimate, but the City shall neither
be obligated nor limited to any specific amount. The City will, if at all possible, restrict
increases to twenty percent (20%) of the estimated quantity and will, if at all possible, restrict
decreases to twenty percent (20%) of the estimated quantity.
28, TERM "OR EQUAL"
A. Where the term "OR EQUAL" is used in these Specifications, the Bidder deviating from
specified item small file with his/her bid a letter fully explaining and justifying his/her proposed
article or equal. The City of South Bend shall be the sole judge in determining if the "OR
EQUAL" offered meets the Specifications.
29. INDEMNIFICATION CLAUSE
A. The Contractor agrees to indemnify, defend, and hold harmless the City of South Bend, its
agents, officers, and employees from all costs, losses, claims and suits, including court costs,
attorney fees, and other expenses, arising from or out of the negligent performance of this
Contract by the Bidder or because or arising out of any defect in the goods, materials or
equipment supplied by the Bidder.
NOTE: Incoming mail does not reach the Board of Public Works until after 9:30 a.m. If
you are sending your bid via Federal Express or another overnight source, please
confirm that your package will arrive before the bid opening time and date.
I MY
vt� Safety Data Sheet
Revision Date Mar-15-2015 Item # 10244
Safety Data Sheet 0235
I. PRODUCT AND COMPANY IDENTIFICATION
Product Name Ferric Chloride Solution DWG Grade
UNlID No, UN2J82 CO!IrT:S::T:AM
E6
f?E
Synonyms Iron (III) Chloride, iron trichloride, FeCb
Recommended Use Water treatment chemical
Uses advised against Consumer uses: Private households (= general public consumers).
Gomp_any Name
PVS Technologies, Inc,
10900 Harper Ave.
Detroit, MI 48213
(313) 571-1100
24 Hour Emergency Phone Number CHEMTREC 1-800-424-9300
2. HAZARDS IDENTIFICATION
DANGER
Hazard statements Causes severe skin burns and eye damage
Harmful if swallowed
Physical hazards Corrosive
May be corrosive to metals
Precatiflonau st tements
Prevention
Res aonce
Storage
Dls os I
Hazar Is not otherwise classified
HNOC_
Other Ir f rmatlon
Otherhazards
• Wear eye/face protection
Wear protective gloves/protective clolhing/eye protection/face protection
Do not breathe dustlfumelgas/miss/vapors/spray
• Do not eat, drink or smoke when using this product
• Wash face, hands and any exposed skin thoroughly after handling
Immediately call a POISON CENTER or doctor/physician
Specific treatment (see section 4 on this Safely Data Sheet)
• Store in a secure area
Dispose of contents/container to an approved waste disposal plant
None known,
Toxic to aquatic life with long lasting effects
Toxic to aquatic life
Page 1 / 8
Item fl 10244 Ferric Chloride Solution DWG Grade
Unknown Acute Toxicity 0.85% of the mixture consists of ingredient(s) of unknown toxicity
3. COMPOSITION/INFORMATION ON INGREDIENTS
Chemical Name
CAS No,
EC No.
Weight-%"
Water
7732-18-6
231.701-2
55-69
Iron trichloride
7705-08-0
231-720.4
31-45
Hydrogen chloride
7647.01-0
231-695.7
0.0-1.0
Ferrous chloride
7758-94-3
231-843-4
0.0-0.7
`The exact percentage (concentration) of composition has been withheld as a trade secret.
4. FIRST AID MEASURES
General advice
Immediate medical attention is required
Eye contact
• Immediate medical attention Is required
Immediately flush with plenty of water. After initial flushing, remove any contact lenses and
continue flushing for at least 15 minutes
• Do not rub affected area
Skin Contact
• Immediate medical attention Is required
• Wash off immediately with soap and plenty of water while removing all contaminated
clothes and shoes
Wash contaminated clothing before reuse
Inhalation
• Call a physician or poison control center immediately
• Remove to fresh air
If not breathing, give artificial respiration
If breathing is difficult, give oxygen
Ingestion
• Cali a physician or poison central center immediately
Do NOT Induce vomiting
• Rinse mouth
• Drink 4 to 8 ounces (120-240 ml) of water or milk as soon as possible after ingaslion.
• Never give anything by mouth to an unconscious person
Note to physician
Product is a corrosive material. Use of gastric lavage or omesis is contraindicated.
Possible perforation of stomach or esophagus should be investigated. Do not give
chemical antidotes. Asphyxia from glottal edema may occur. Marked decrease in blood
pressure may occur with moist rates, frothy spLitum, and high pulse pressure. Treat
symptomatically.
Self-protectlon for first aid
Use personal protective equipment as required. Avoid contact with skin, eyes or clothing.
personnel
5. FIRE -FIGHTING MEASURES
Suitable extinguishing media
• Dry chemical, CO2, water spray or alcohol -resistant foam
Use extinguishing measures that are appropriate to local circumstances and the
Unsuitable extinguishing media
surrounding environment
• Caution; Use of water spray when fighting fire may be inefficient
Do not use a solid water stream as it may scatter and spread fire
Specific hazards arising from the
chemical
- The product causes burns of eyes, skin and mucous membranes
- Thermal decomposition can lead to release of Irritating and toxic gases and vapors
In the event of fire and/or explosion, do not breathe fumes
Page 218
Item 0 10244 Ferric Chloride Solution QWG Grade
Protective equipment and
Wear a self-contained breathing apparatus and chemical protective clothing
precautions for firefighters
Flammable properties
No information available
Explosive properties
No information available
6, ACCIDENTAL RELEASE MEASURES
Personal precautions
Evacuate personnel to safe areas
+ Use personal protective equipment as required
Avoid contact with skin, eyes or clothing
Keep people away from and upwind of spilltleak
Environmental precautions
• For small spills, absorb material with clay absorbent or other compatible material.
Dispose of the waste material according to local, state and governmental requirements.
• For large spills, contain the material using barriers of absorbent pigs, clay absorbent or
earth dams.
+ US regulations require reporting spills of this material that could reach any surface waters.
The toil -free phone number for the US Coast Guard National Response Center is
1-800-424-8802
Methods for cleaning up
Neutralize with soda ash or lime
+ Take up mechanically, placing in appropriate containers for disposal
• Clean contaminated surface thoroughly
• Soak up with inert absorbent material
Other Information
• Spills exceeding the Reportable Quantity (RQ) of 1000 pounds or more must be reported
to the National Response Center, (800) 424-8802.
7, HANDLING AND STORAGE
Advice on safe handling Use personal protective equipment as required
Avoid contact with skin, eyes or clothing
Ensure adequate ventilation, especially in confined areas
In case of Insufficient ventilation, wear suitable respiratory equipment
Use only with adequate ventilation and In closed systems
Storage Conditions Keep container lightly closed in a dry and well -ventilated place
• Keep out of the reach of children
Keep containers tightly closed in a dry, cool and well -ventilated place
Keep in properly labeled containers
Incompatible materials Incompatible with strong acids and bases, oxidizers, steel, and most metals
8, EXPOSURE CONTROMPERSONAL PROTECTION
Chomicai Name
ACGIH TLV
OSHA PEL
NIOSH Ipl_H
Iron trichlorlde
TWA: 1 mg/m3 Fe
TWA: 1 mg1m3 Fe
7705-08-0
Hydrogen chloride
Calling: 2 ppm
Ce€ling: 5 ppm
IDLH; 50 ppm
7647.01.0
Cellfng: 7 mglm3
Colling: 5 PPm
Ferrous chloride
TWA: 1 mglm3 Fe
(vacated) TWA: 1 mghO Fe
Calling: 7 m Im3
TWA: 1 mgl0 Fe
7758-44-3
Ex ostrre Guidelines ,
Engineering Controls Ensure adequate ventilation, especially In confined areas.
Individual protection_m,easures, such as personal protective equipment
Respiratory protection - A respiratory protection program that meets OSHA 1910,134 and ANSI Z88.2
requirements must be followed whenever workplace conditions warrant the use of a
rospriator.
Page 318
Item tf 10244 Ferric Chloride Solution DWG Grade
Eye/Face protection
• Tight sealing safely goggles
• Face protection shield
Skin and body protection
Wear suitable protective clothing
{ Wear impervious protective clothing, including boots, gloves, lab coat, apron or coveralls,
as appropriate, to prevent skin contact
General Hygiene Considerations
Do not eat, drink or smoke when using this product
• Wash contaminated clothing before reuse
• Contaminated work clothing should not be allowed out of the workplace
Regular cleaning of equipment, work area and clothing is recommended
Avoid contact with skin, eyes or clothing
9. PHYSICAL AND CHEMICAL PROPERTIES
Information on,baslc ph afc I air
chemical ro ernes
Physical state
Liquid
Appearance
Clear to slightly hazy
Color
Red brown
Odor
Slight Iron acidic
Odor threshold
No information available
Property_
PH
Melting polnt/Froezing Point
Boiling point 1 boiling range
Flash point
Evaporation rate
Flaminablilty (solid, gas)
Flammability L.Imit In Air
Upper flammability limit (%I
Lower flammability limit (%};
Vapor pressure
Vapor density
Specific Gravity
Water solubility
Solubility In other solvents
Partition coefficient
Autolgnnition temperature
Decomposition temperature
Kinematic viscosity
Dynamic viscosity
Explosive properties
Oxidizing properties
Other Information
Softening port °C
Molecular welght
VOC Content
Density
Bulk density
Values
<2
•26 °C / -15 °F
110 °C / 230 °F
No Information available
<1
No information available
No information available
No information available
No information available
No information available
1.40
Miscible in water
No information available
No information available
No information available
No information available
No Information available
No information available
No information available
No Information available
No Information available
No information available
No Information' available
No information available
11,7 Pounds per gallon (lb/gal), Typical
Remarks • Method
n-Butyl acetate =1
Not flammable
negligible
10, STABILITY AND. REACTIVITY
Stability Stable under recommended storage conditions
Conditions to avoid • Exposure to air or mo€stun over prolonged periods
Incompatible materials • Incompatible with strong acids and bases, oxidizers, steel, and most melafs
Page 4 / 8
Item # 10244 Ferric Chloride Solution QWG Grade
Hazardous Decomposition Products • Thermal decomposition can lead to release of Irritating and toxic gases and vapors
Possibility of Hazardous Reactlons - None under normal processing and storage
11_. TOXICOLOGICAL INFORMATION
Information on like!y routes of exposure
Principle Routes of Exposure Inhalation Skin Contact Eye contact
Inhalation May cause Irritation of respiratory tract. Avoid breathing vapors or mists,
Ingestion May cause adverse kidney effects, May cause adverse liver effects.
Skin Contact Contact causes severe skin irritation and possible burns,
Eye contact Corrosive to the eyes and may cause severe damage including blindness.
chemical Name
Oral L060
Dermal LD60
Inhalatlon LC60
Iron trichloride
7705.08-0
= 450 mglkg { Rpt)
>2000 m tk (rat)
g g {
Hydrogen chloride
7647.01.0
= 700 mglkg { Rat }
> 5010 mglkg { Rabbit }
= 3124 ppm ( Rat ) 1 h
Ferrous chloride
450
7758-94.3
Information on toxicological effects
Symptoms Vomiting, Hypoxemia (reduced 02 in the blood), Metabolic Acidosis
Delayed and ImMpdlate ffe is s well art chronic eff cts from short and long-term exposure
Sensitization No information available.
Germ cell mutageniclty No information available.
CarcInogenlolty No Information available
Chemical Name I
ACQIH
IARC
NTP
OSHA
Hydrogen chloride
Group 3
7847.01.0
wAw LY rvu Imurmauon avatiaote.
STOT - single exposure No Information available.
STOT - repeated exposure No information available.
Chronic toxicity Chronic exposure to corrosive fumeslgases may cause erosion of the teeth followed by jaw
necrosis. Bronchial irritation with chronic cough and frequent attacks of pneumonia are
common, Gastrointestinal disturbances may also be seen. Avoid repeated exposure.
Possible risk of Irreversible effects. May cause adverse liver effects.
Target Organ Effects Eyes, Gastrointestinal tract (GI), Liver, Respiratory system, Skin.
Aspiration hazard No information available,
Numerical measures of toxic) -...Product Information
Unknown Acute Toxicity 0.85% of the mixture consists of ingredient(s) of unknown toxicity
The following values are calculated based on chapter 3,1 of the GHS documont . mg/kg
Eco xlclt
Ecoloxicity
0"1% of the mixture consists
chemical Name
Iron trlchloride
7705.08.0
Persistence and dg radablllt
Bloacctrmulation
12. ECOLOGICAL INFORMATION
Toxic to aquatic life with long lasting effects
MDonentslsl of unknown hnyn Mr +r. +hn n
uatic plants Fish
20.96 • 22,66: 96 h Pirnephales
promelas mg/L LC60 semi -static
20,26: 06 h Lepomis macrochirus
mg/L LC50 semi -static
No information available.
No information available
Page 51 8
27.9: 48 h Daphnia magna mg/L
EC50 9.6: 48 h Daphnia magna
mg/L EC50 Static
Item # 10244 Ferric Chloride Solution DWG Grade
Other adverse effects No information available
13, DISPOSAL CONSIDERATIONS
Disposal of wastes - This material, as supplied, is a hazardous waste according to federal regulations (40 CFR
261)
Contaminated packaging + Do not reuse container
US EPA Waste Number + D002
This product contains one or more substances that are listed with the State of California as a hazardous waste.
Chemical Name California Hazardous Waste Status
Iron^Irichlorlde IToxic
DOT
Proper shipping name
Hazard Class
UNIID No,
Packing Group
RQ (lbs)(dry)
RQ as Is (lbs)(wet)
Description
Special Provisions
Emergency Response Guide
Number
IATA
UN/ID No.
Proper shipping name
Hazard Class
Packing Group
ERG Code
Special Provisions
IMDG
UN/ID No.
Proper shipping name
Hazard Class
Packing Group
EmS•No,
Special Provisions
SARA 1 112 Haxard Ca.testorles
14. TRANSPORT INFORMATION
FERRIC CHLORIDE, SOLUTION
8
UN2582
1000
2222 (45% Ferric Chloride)
UN2582, Ferric chloride, solution, 8, lit
015, I83, T4, TP1
154
UN2582
FERRIC CHLORIDE SOLUTION
8
8L
A3
UN2582
FERRIC CHLORIDE, SOLUTION
8
F-A, S-B
223
15, REGULATORY INFORMATION
Acute health hazard Yes
Chronic Health Hazard Yes
Fire hazard No
Sudden release of pressure hazard No
Reactive Hazard No
SARA 313 Section 313 of Title III of the Superfund Amendments and Reauthorization Act of 1986
(SARA), This product does not contain any chemicals which are subject to the reporting
requirements of the Act and Title 40 of the Code of Federal Regulations, Part 372
page 618
Item It 10244 Ferrlc Chloride 901utlon DWG Grade
CWA Clean Water Ac This product contains the following substances which are regulated pollutants pursuant to
the Clean Water Act (40 CFR 122.21 and 40 CFR 122.42)
Chemical Name
CWA • Reportable
CWA • Text(; Pollutants
CWA • Priority Pollutants
CWA - Hazardous
Quantities
Substances
Iron trichloride
1000 tb
X
7705.08-0
Hydrogen chloride
600014
X
7647.01-0
Ferrous chloride
100 lb
X
7758.94.3
CERCLA This material, as supplied, contains one or more substances regulated as a hazardous
substance under the Comprehenslve Environmental Response Compensation and Liability
Act CERCLA Mn CFR 302
Chemical Name
Hazardous Substances RQs
CERCLAISARA RQ
RQ Ibs d ryL
Iron trichloride
100016
RQ 1000 lb final RQ
7706-08-0
RQ 454 k Final RQ
Hydrogen chloride
500016
Y
�000 lb
RQ 5000 lb final RQ
7647.01-0
RQ 2270 kg final RQ
Ferrous chloride
100 lb
RQ 100 lb final RQ
7758.94.3
RQ 46.4 kq final RQ
I IC Q4s., Dn`.,1../1,.--
v �u �v v uIgu V110
Callfornla Propasttlon 86
U.S• Stat_Q Right -to -Know
Regulations
This product does not contain any Proposition 65 chemicals
Chemical Name
New Jerae
Massachusetts
Pennsylvania
Iron trichloride
X
X
X
7705-08-0
Ferrous chloride
X
X
X
7758-94-3
Chernical Narne U.S. • DEA • List I or Precursor U.S.• DEA • List II or Essential
Chemicals Chemicals
Hydrogen chloride 50 gallon, Export Volume
7647-01.0 27 kg, Export Weight
0 kg, Domestic Sales Wel ht
International Inventorles
ISCA
DSLINDSL
EINECSIELINCS
ENCS
IECSC
KECL
PICCS
AICS
Complies
Complies
Complies
Does not comply
Complies
Complies
Complies
Complies
Ise end:
TSCA - Untied States Toxic Substances Control Act Seclion 8(b) lnventery
DSLINDSL • Canadian Domestic Substances LIst/Non-Domestic Substances List
EINECSIELINCS - European Inventory of Existing Chemical Substances/European List of Notified Chemical Substances
ENCS • Japan Existing and New Chemlcal Substances
IECSC - China Inventory of Existing Chemical Substances
KECL - Korean Existing and Evaluated Chemical Substances
PICCS - Phllippines inventory of Chemicals and Chemical Substances
AICS - Australian Inventory of Chemical Substances
16. OTHER INFORMATION
Page 7 / 8
Item # 10244 Ferric Chloride Solution DWG Grade
NFPA Health hazards 3 Flammability 0
W IS Health hazards 3 Flammability 0
Instability 0 Physical and Chemical
Properties -
Physical hazards 0 Personal protection D
Item 11 10244
Safety Data Sheet 0236
Revision Date Mar-15-2015
Issue Date Mar-15.2015
Version 1
Revision Note "*" Updaled value on SDS.
Disclalmer
All Information, statements, data, advice, andlor recommendations, Including, without limitation, those relating to
storage, loadinglunloading, piping, and transportation (collectively referred to herein as "Information") are believed to be
accurate, reliable, and based on reliable Industry and regulatory references. However, no representation or warranty,
express or Implied, Is made as to Its completeness, accuracy, fitness for a particular purpose or any other matter,
Including, without limitation, that the practice or application of any such information is free of patent Infringement or
other Intellectual property misappropriation. The Company providing this SDS Is not engaged In the business of
providing technical, operational, engineering, or safety Information for a fee, and therefore, any such information
provided herein has been furnished as an accommodation and without charge, All Information provided herein Is
Intended for use by persons having requisite knowledge, skill, and experience In the chemical Industry. The Company
providing this SDS shall not be responsible or liable for the use, application, or Implementation of the Information
provided herein, and all such Information Is to be used at the risk, and In the sole Judgment and discretion of such
persons, their employees, advisors, and agents, This safety data sheet (SDS) Is offered for your Information,
consideration, and Investigation as required by federal hazardous products act and related legislation.
End of Safety Data Sheet
Page 8 18
r F
Technical Speciffcatio;i Sfjeet
Li uid Ferric Chloride -- Drinking Water Grade
PVS Technologies Liquid Ferric Chloride is a concentrated solution of Iron III Chloride (FeC13) in
water. It is manufactured from 100% high purity raw materials.
Principal Uses
Potable Water Treatment
• Turbidity reduction
0 Color elimination
• Enhanced coagulation, NOM and DBP precursor removal
• Softening solids sedimentation
• Lead control through a wide p€-I application range
Sludge reduction
• Filter conditioning
* Arsenic Removal
Wastewater Treatment
• Phosphate precipitation and removal
• Enhanced sedimentation
0 Dewatering of aN types of sludge streams
• Polymer flocculent enhancement
• Sulfide based odor elimination
0 Struvite control
Specifications
Appearance -
Concentrations:
FeCI3
FeC12
Free Acid as HCI
lnsolubles
Radionuclides
S ecific ravit :
V€scoslt :
Cr stallizat€on.
AWWA Certification:
ANSI/NSF Standard 60 Certification:
CAS No.;
UN Classification:
Doctiment Number, Page 1 of 2
TAFU017
A dark red/brown liquid
37% - 42%
0.75% maximum
1.0% maximum Drinkin Water Grade
0.008% 80 m maximum
None
1.38 — 1.49
12.1 centi oises for a 40% solution
37% FeCia - 150E ; 40% FeCl3 10°F
B407-12
Max€mum use level — 250 PPM as solution
UN2582 Ferr€c Chloride Solution
SQC data available on request
Revision No,: Revision
2 AAMAII)r..ta
Technical Specification Sheet
Delivery
cy$!10
t�r,r-;
This product is available for shipping via the following options:
55 gallon drums
300 gallon totes
4,000 & 8,000 gallon tank trucks
17,000 gallon railcars
Product Availability
Throughout North America -- 8,000 gallon tankers only available in Michigan,
Handling & Safety
Ferric Chloride is considered to be hazardous by definition of the Hazard Communication
Standard (29 CFR 1910.1200) and should be handled in a manner that is consistent with
acceptable practices. Please obtain the Ferric Chloride Safety Data Sheet for complete up-to-
date information.
Under normal situations the only protective equipment required in the use and handling of Liquid
Ferric Chloride are splash proof chemical goggles and rubber gloves. Liquid Ferric Chloride will
stain both clothing and skin and it is recommended that, to protect against this occurrence, other
protect clothing be worn as is appropriate.
Ferric Chloride reacts with many metals, However, most handling situations are reliably
addressed through the use of common plastic materials such as FRP, PVC, Polyethylene,
Polypropylene and Teflon. For additional information, please consult your equipment supplier.
For additional information call: 313 571.1100
To place an order call: 800 337.7428
PVS Technologles - Serving Water and Wastewater Plants throughout the World
This bulletin and the information contained herein are offered solely for your consideration, investigation
and verification, NO REPRESENTATIONS OR WARRANTIES, EXPRESS OR IMPLIED, OF
MERCHANTABILITY OR OTHERWISE, ARE MADE OR CONTAINED HEREIN. PVS Technologies'
exclusive responsibility for any claims, including claims based on negligence, arising in connection with
the information contained herein or the subsequent purchase, use, storage or handling of the product will
in no event exceed PVS Technologies' sale price for the product with respect to which damages are
claimed. In no event will PVS Technologies be liable for any incidental or consequential damages arising
in connection with the Information contained herein or the subsequent purchase, use, storage or handling
of the product, User accepts full responsibility for compliance with all applicable Federal, State and Local
laws and regulations. Nothing contained herein will be construed to constitute permission or a
recommendation to use the product in any process or formulation covered by a patent a patent
application owned by PVS Technologies or by others.
Do�TAFU017
Number: �ag oco)f 2 Revision No.:
Revision Date:
2 RixlhG1nnnr_
The Public Health and Safety Organization
NSF Product and Service Listings
These NSF Official Listings are current as of Friday, January 26, 2oi8 at 12:15 a.m. Eastern Time, Please
contact NSF International to confirm the status of any Listing, report errors, or make suggestions.
Alert: NSF is concerned about fraudulent downloading and manipulation of website text, Always confirm this
information by clicking on the below link for the most accurate information:
htt info.nsf.or Certified PwsChemicals Listin s.as ?Com an = 2U6 o&Standard=oho&
NSF/ANSI Go
Drinking Water Treatment Chemicals - Health Effects
PVS Technologies
10goo Harper Avenue
Detroit, MI 48213
United States
313-571-1100
Visit this company's website
(htti)://www.pvschemicals.com)
Facility: Decatur, AL
Ferrous Chloride[Y1
n-ade Designation Product Flmction Max Use
Ferrous Chloride, Solution Other 25omg/L
Liquid Ferrous Chloride Other 25omg/L
Liquid Ferrous Chloride- DWG Other 25omg/L
[11 This product may be used For chlorite removal.
NOTE: Only products bearing the NSF Mark on the product, product packaging, and/or
documentation shipped with the product are Certified.
http://info.nsf-arg/Certified/PwSChemicals/Listings.asp?Company=3U690&Standard=060 118
1I26/2918
Listing Category Search Page j NSF International
Facility: Trinity, AL
Ferrous Chloride[il
Trade Designation
Ferrous Chloride, Solution
Liquid Ferrous Chloride
Liquid Ferrous Chloride- DWG
Product Function
Coagulation & Flocculation
Coagulation & Flocculation
Coagulation & Flocculation
[1] This product may be used for chlorite removal.
Max Use
25omg/L
25omg/L
25omg/L
NOTE: Only products bearing the NSF Mark on the product, product packaging, and/or
documentation shipped with the product are Certified,
Facility: Distribution Center - Henderson, CO
Ferric Chloride
Trade Designation Product Function Max Use
Ferric Chloride Solution Coagulation & Flocculation 25omg/L
LFC Coagulation & Flocculation 25omg/L
LFC DWG Coagulation & Flocculation 25omg/L
Liquid Ferric Chloride Coagulation & Flocculation 25omg/L
Liquid Ferric Chloride Drinking Water Grade Coagulation & Flocculation 25omg/L
Polymer Blends[PY]
n-ade Designation
Product Function
Max Use
Ferri+Plus 1005
Coagulation & Flocculation
251mg/L
Ferri+Plus logo
Coagulation & Flocculation
253mg/L
Ferri+Plus 1020
Coagulation & Flocculation
255mg/L
Ferri+Plus 1050
Coagulation & Flocculation
16omg/L
Ferri+Plus 1075
Coagulation & Flocculation
107mg/L
Ferri+Plus 11oo
Coagulation & Flocculation
8omg/L
Ferri+Plus 1125
Coagulation & Flocculation
64mg/L
Ferri+Plus 1150
Coagulation & Flocculation
53mg/L
Fermi+Plus 1200
Coagulation & Flocculation
4omg/L
Ferri+Plus 1300
Coagulation & Flocculation
27mg/L
Ferri+Plus 1400
Coagulation & Flocculation
2omg/L
http://info,nsf.orgICertifiedIPwsChemicalsIListings.asp?Company=3U690&Standard=060 218
1(26/2��8 Listing Category Search Page I NSF International
[PY] Polyamines Certified by NSF International comply with 40 CFR 141.111 requirements for
percent monomer and dose.
Facility: Augusta, GA
Ferric Chloride
Trade Designation
Ferric Chloride, Solution
LFC
LFC-DWG
Liquid Ferric Chloride
Liquid Ferric Chloride Drinking Water Grade
(DWG)
Facility: Distribution Center - Chicago, IL
Ferric Chloride
7)-ade Designation
Ferric Chloride, Solution
Liquid Ferric Chloride
Liquid Ferric Chloride - DWG
Product Function
Coagulation & Flocculation
Coagulation & Flocculation
Coagulation & Flocculation
Coagulation & Flocculation
Coagulation & Flocculation
Product Function
Coagulation & Flocculation
Coagulation & Flocculation
Coagulation & Flocculation
Facility: Distribution Center - East St. Louis, IL
Ferric Chloride
Trade Designation
Ferric Chloride, Solution
Liquid Ferric Chloride
Liquid Ferric Chloride - DWG
Ferrous Chloride
Dade Designation
Ferrous Chloride
Ferrous Chloride, Solution
Liquid Ferrous Chloride
Product Function
Coagulation & Flocculation
Coagulation & Flocculation
Coagulation & Flocculation
Product Function
Coagulation & Flocculation
Coagulation & Flocculation
Coagulation & Flocculation
Max Use
25omg/L
25omg/L
25omg/L
25omg/L
25omg/L
Max Use
25omg/L
25omg/L
25omg/L
Max Use
25omg/L
25omg/L
25omg/L
Max Use
25omg/L
25omg/L
25omg/L
httpalinfo.nsf.org/Certified/PwsChamicaIs/Listings.asp?Company=3U690&Standard=060 318
11612Q;j 8 Listing Category Search Page f NSF International
NOTE; Only products bearing the NSF Mark are NSF Certified.
Facility: Distribution Center - Louisville, KY
Ferric Chloride
Trade Designation
Ferric Chloride DWG
Ferric Chloride Drinking Water Grade
Ferric Chloride, Solution
Liquid Ferric Chloride
Product Function Max Use
Coagulation & Flocculation 125mg/L
Coagulation & Flocculation 125mg/L
Coagulation & Flocculation 125mg/L
Coagulation & Flocculation 125mg/L
Facility: Distribution Center - 2 Baltimore, MD
Ferric Chloride
node Designation Product Function Max Use
Ferric Chloride, Solution Coagulation & Flocculation 250mg/L
Liquid Ferric Chloride Coagulation & Flocculation 25omg/L
Liquid Ferric Chloride -DWG Coagulation & Flocculation 25omg/L
Facility: Detroit, MI
Ferric Chloride
Dade Designation
Product Function
Max Use
Ferric Chloride Solution
Coagulation & Flocculation
25omg/L
Ferric Chloride, Solution
Coagulation & Flocculation
25omg/L
LFC
Coagulation & Flocculation
25omg/L
LFC-DWG
Coagulation & Flocculation
25omg/L
Liquid Ferric Chloride
Coagulation & Flocculation
25omg/L
Liquid Ferric Chloride Drinking Water Grade
Coagulation & Flocculation
25omg/L
(DWG)
Liquid Ferric Chloride LMG
Coagulation & Flocculation
25omg/L
Polyiner Blends[PY]
Trade Designation
Product Function
Max Use
Ferri+Plus 1005
Coagulation & Flocculation
251mg/L
Ferri+Plus 1olo
Coagulation & Flocculation
253mg/L
Ferri+Plus 1020
Coagulation & Flocculation
255mg/L
Ferri+Plus 1025
Coagulation & Flocculation
25omg/L
http:llinfo,nsf,org/Certified]PwsChemicals/Listings.asp?Company=3U690&Standard=060 418
1/?612(11,II
Listing Category Search Page I NSF International
Ferri+Plus 1O50
Coagulation & Flocculation
16omg/L
Ferri+Plus 1075
Coagulation & Flocculation
1O7mg/L
Ferri+Plus 11Oo
Coagulation & Flocculation
Somg/L
Ferri+Plus 1125
Coagulation & Flocculation
64mg/L
Ferri+Plus 1150
Coagulation & Flocculation
53mg/L
Ferri+Plus 1200
Coagulation & Flocculation
4omg/L
Ferri+Plus 130o
Coagulation & Flocculation
2-7mg/L
Ferri+Plus 1400
Coagulation & Flocculation
2omg/L
Ferri+Plus 2005
Coagulation & Flocculation
251mg/L
Ferri+Plus 2010
Coagulation & Flocculation
253mg/L
Ferri+Plus 202O
Coagulation & Flocculation
255mg/L
Ferri+Plus 2050
Coagulation & Flocculation
263mg/L
Ferri+Plus 2075
Coagulation & Flocculation
267mg/L
Ferri+Plus 210o
Coagulation & Flocculation
loomg/L
Ferri+Plus 2125
Coagulation & Flocculation
Somg/L
Ferri+Plus 2150
Coagulation & Flocculation
66mg/L
Ferri+Plus 2200
Coagulation & Flocculation
5omg/L
Ferri+Plus 23O0
Coagulation & Flocculation
33mg/L
Ferri+Plus 2400
Coagulation & Flocculation
25mg/L
Ferri+Plus 3005
Coagulation & Flocculation
251mg/L
Ferri+Plus 3010
Coagulation & Flocculation
253mg/L
Ferri+Plus 302O
Coagulation & Flocculation
255mg/L
Ferri+Plus 3050
Coagulation & Flocculation
263mg/L
Ferri+Plus 3075
Coagulation & Flocculation
267mg/L
Ferri+Plhls 3100
Coagulation & Flocculation
ioomg/L
Ferri+Plus 3125
Coagulation & Flocculation
Somg/L
Ferri+Plus 3150
Coagulation & Flocculation
66mg/L
Ferri+Plus 32O0
Coagulation & Flocculation
50mg/L
Ferri+Plus 3300
Coagulation & Flocculation
33mg/L
Ferri+Plus 3400
Coagulation & Flocculation
25mg/L
Ferri+Plus 4005
Coagulation & Flocculation
25img/L
Ferri+Plus 4010
Coagulation & Flocculation
253mg/L
Ferri+Plus 4020
Coagulation & Flocculation
255mg/L
Ferri+Plus 4O50
Coagulation & Flocculation
263mg/L
Ferri+Plus 4075
Coagulation & Flocculation
267mg/L
Ferri+Plus 4100
Coagulation & Flocculation
loomg/L
Ferri+Plus 4125
Coagulation & Flocculation
Somg/L
Ferri+Plus 4150
Coagulation & Flocculation
66mg/L
Ferri+Plus 4200
Coagulation & Flocculation
5omg/L
Ferri+Plus 4300
Coagulation & Flocculation
33mg/L
Ferri+Plus 44O0
Coagulation & Flocculation
25mg/L
Ferri+Plus 5005
Coagulation & Flocculation
251mg/L
Ferri+Plus 5010
Coagulation & Flocculation
253mg/L
Ferri+Plus 5O20
Coagulation & Flocculation
255mg/L
htlp:11info.nsf.org/Certified[PwsChemicals/Li sting s,asp?Company=3U690&Standard=060
518
11176/2,01,8
Listing Category Search Page I NSF International
Ferri+Plus 5050
Coagulation & Flocculation
263mg/L
Ferri+Plus 5075
Coagulation & Flocculation
267mg/L
Ferri+Pius 5100
Coagulation & Flocculation
loorng/L
Ferri+Plus 5125
Coagulation & Flocculation
8omg/L
Ferri+Plus 5150
Coagulation & Flocculation
66mg/L
Ferri+Plus 5200
Coagulation & Flocculation
50mg/L
Ferri+Plus 5300
Coagulation & Flocculation
33mg/L
Ferri+Plus 5400
Coagulation & Flocculation
25mg/L
[PY] Po.lyamines Certified by NSF International comply with 40 CFR 141.111 requirements -for
percent monomer and dose.
Facility: Distribution Center - Lakeville, MN
Ferric Chloride
Trade Designation
Ferric Chloride, Solution
Liquid Ferric Chloride
Liquid Ferric Chloride - DWG
Product Function
Coagulation & Flocculation
Coagulation & Flocculation
Coagulation & Flocculation
Facility: Distribution Center - 1 Philadelphia, PA
Ferric Chloride
n-ade Designation
Ferric Chloride, Solution
Liquid Ferric Chloride
Liquid Ferric Chloride - DWG
Product Function
Coagulation & Flocculation
Coagulation & Flocculation
Coagulation & Flocculation
Facility: Distribution Center - Fort Worth, TX
Ferric Chloride
Trade Designation
Ferric Chloride, Solution
Liquid Ferric Chloride
Liquid Ferric Chloride - DWG
Product Function
Coagulation & Flocculation
Coagulation & Flocculation
Coagulation & Flocculation
Max Use
25omg/L
25omg/L
25omg/L
Max Use
25omg/L
25omg/L
25omg/L
Max Use
25omg/L
25omg/ L
25omg/L
http://info,nsf.org/Certified/PwsChemicaIs/Listings.asp?Company=3U690&Standard=060 618
112
Listing Category Search Page I NSF International
Facility: Houston, TX
lrerric Chloride
Trade Designation
Ferric Chloride LMG
Ferric Chloride Solution DWG (LFCD)
Ferric Chloride Solution EMD
Ferric Chloride Solution LMG
Ferric Chloride, Solution
LFC
LFC-DWG
Liquid Ferric Chloride
Liquid Ferric Chloride Drinking Water Grade
(DWG)
Product Function
Max Use
Coagulation & Flocculation
25omg/L
Coagulation & Flocculation
25omg/L
Coagulation & Flocculation
250mg/L
Coagulation & Flocculation
250mg/L
Coagulation & Flocculation
25omg/L
Coagulation & Flocculation
25omg/L
Coagulation & Flocculation
25omg/L
Coagulation & Flocculation
25omg/L
Coagulation & Flocculation
25omg/L
Facility: Distribution Center - Petersburg, VA
Ferric Chloride
7�-ade Designation P►•oductFunction Max Use
Ferric Chloride, Solution Coagulation & Flocculation 25omg/L
Liquid Ferric Chloride Coagulation & Flocculation 25omg/L
Liquid Ferric Chloride - DWG Coagulation & Flocculation 25omg/L
Facility: New Martinsville, WV
Feri-ic Chloride
7yade Designation Pi-oduct FYmction Max Use
Ferric Chloride Solution DWG Grade Coagulation & Flocculation 25omg/L
Ferric Chloride, Solution Coagulation & Flocculation 25omg/L
Liquid Ferric Chloride Coagulation & Flocculation 25omg/L
Liquid Ferric Chloride Drinking Water Grade Coagulation & Flocculation 25omg/L
(DWG)
Liquid Ferric Chloride LMG Coagulation & Flocculation 25omg/L
Polymer Blends[PY]
7O-ade Designation Product Function Max Use
Ferri+Plus ioo5 Coagulation & Flocculation 251mg/L
htip:Flinfo.nsf.orglCertifiedlPwsChemicalsllistings.asp7Company=3U680&Standard=060
718
1/2p/201$
Listing Category Search Page J NSF International
Ferri+Plus iolo
Coagulation & Flocculation
253mg/L
Ferri+Plus io2o
Coagulation & Flocculation
255mg/L
Ferri+Plus 1025
Coagulation & Flocculation
25omg/L
Ferri+Plus 1050
Coagulation & Flocculation
16omg/L
Ferri+Plus 1075
Coagulation & Flocculation
107mg/L
Ferri+Plus 11oo
Coagulation & Flocculation
8omg/L
Ferri+Plus 1125
Coagulation & Flocculation
64mg/L
Ferri+Plus 1150
Coagulation & Flocculation
53mg/L
Ferri+Plus 1200
Coagulation & Flocculation
4omg/L
Ferri+Plus 1300
Coagulation & Flocculation
27mg/L
Ferri+Plus 1400
Coagulation & Flocculation
2omg/L
[PY] Polyamines Certified by NSF International comply with 40 CFR 141.111 requirements for
percent monomer and dose.
Number of matching Manufacturers is i
Numher of matching Products is 144
Processing time was o seconds
http:/Iinfo.nsf,arg/CertifiedlPwsChemicaIsIListings.asp?Company=3U690&Standard=060 8/8