Laserfiche WebLink
The location,of kitchen ventilating fans when vented by duct system <br />shall be placed A least four (4) feet above cooking unit. If vented <br />directly through an outside wai'1 with no duct system except the fan, <br />housing, no regulation as to location is hereby specified. <br />INSTALLATION - OIL BUW..,'=g 701j 410T <br />(Burners, Controls, Apparatus, ate) <br />1. Combustion Safeguards. Each oilburner shell be provided with an <br />approved automatic combustion safeguard which will effectively proven-c <br />the abnormal discharge of oil in case of ignition failure or flame <br />failure. <br />a. Heat vaporization burners shall be provided with an approved <br />constant level and anti- flooding device. <br />b. Oil burners other than heat vaporization burners whose firing <br />rate does not exceed five (5) gallons per hour shall be provided <br />with an approved combustion safeguard device whose main burner <br />trial- for - ignition or flame failure timing period does not exceed <br />two (2) minutes. <br />c. Oil burners whose firing rate exceeds five (5) gallons per hour <br />shall be provided with an approved combustion safeguard whose main <br />burner, trial- for - ignition timing does not exceed sixty (60) <br />seconds, d <br />hex- �16')"aesortde. <br />2. Domestic Type Rotary Vaporization Burners. Domestic Type vaporization <br />burners which operate on the vertical rotary principal shall be pre - <br />vided with constant level device arranged.so as to prevent an abnor- <br />mal supply of oil to the burner. <br />3. Limit Controls. till oil burning equipment shall be provided with an <br />approved means of automatically shutting off the burner when the <br />limits of temperature and /or pressure here inafter.specified are ex- <br />ceedod; except that this requirement shall not apply to oil fired <br />foom heaters. In the case of a heat vaporization burner, this <br />control may place the burner on low -flame operation. <br />a. The setting of the limit control on a mechanical warm air furnace <br />shall not exceed 20OF except by special permission of the <br />Department. <br />b. The setting of the limit control on a gravity warm air furnace <br />shall not exceed 300F. <br />c. The setting of the limit control on a steam boiler shall not <br />exceed the allowable working pressure of the boiler. <br />d. The setting of the limit control on a boiler or heater used in <br />connection with a hot water heating or a hot water supply <br />system shall not exceed 20OF except by special permission of <br />the Department. <br />4. Low Water Fuel Cutoff. As required by the American Society of <br />Mechanical ngineers boiler Code, a low water fuel cutoff shall be <br />installed in accordance therewith on all oil fired steam boilers. <br />5. Limit Control & Low Mater Fuel Cutoff in 114ain Circuit. Limit <br />Controls and low water fuel cutoffs which, by operating, interrupt <br />the electric power supply to the burner shall be so arranged as to <br />open the main line current supply to the burner, whether the switch- <br />ing is integral with the sensing element or remote from same. <br />6. Combustion air - Oil Interlock. In installations equipped with forced <br />or induced draft fans, or both, approved means shall be provided to <br />immediately shut off the oil supply upon air supply failure. Controls <br />actuated by failure of the power supply to the blower motor do net <br />meet this requirement. This does not apply to heat vaporization <br />burners listed by Underwriters' Laboratories, Inc. <br />