My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
25-20 Resolution to Approve the Issuance of Scrap Metal / Junk Dealers / Recycling Operation Licenses
sbend
>
Public
>
Common Council
>
Legislation
>
Upcoming Bills
>
2025
>
04-14-2025
>
25-20 Resolution to Approve the Issuance of Scrap Metal / Junk Dealers / Recycling Operation Licenses
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
4/1/2025 1:24:34 PM
Creation date
4/1/2025 1:23:56 PM
Metadata
Fields
Template:
City Council - City Clerk
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
168
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
Show annotations
View images
View plain text
STATUS CODE DESCRIPTION <br /> p.:S'S 5303.5.3-Securing Compressed gas containers,cylinders and tanks shall be secured to prevent <br /> compressed gas containers, falling caused by contact,vibration or seismic activity.Securing of compressed <br /> cylinders and tanks gas containers,cylinders and tanks shall be by one of the following methods: 1. <br /> Securing containers,cylinders and tanks to a fixed object with one or more <br /> restraints.2.Securing containers,cylinders and tanks on a cart or other mobile <br /> device designed for the movement of compressed gas containers,cylinders or <br /> tanks.3.Nesting of compressed gas containers,cylinders and tanks at container <br /> filling or servicing facilities or in seller's warehouses not accessible to the public. <br /> Nesting shall be allowed provided the nested containers,cylinders or tanks,if <br /> dislodged,do not obstruct the required means of egress.4.Securing of <br /> compressed gas containers,cylinders and tanks to or within a rack,framework, <br /> cabinet or similar assembly designed for such use.Exception:Compressed gas <br /> containers,cylinders and tanks in the process of examination,filling,transport or <br /> servicing. <br /> PASS 605.1 -Abatement of Identified electrical hazards shall be abated.Electrical wiring,devices,appliances <br /> electrical hazards and other equipment that is modified or damaged and constitutes an electrical <br /> shock or fire hazard shall not be used. <br /> PASS 605.3-Working space and A working space of not less than 30 inches(762 mm)in width,36 inches(914 mm) <br /> clearance in depth and 78 inches(1,981 mm)in height shall be provided in front of electrical <br /> service equipment.Where the electrical service equipment is wider than 30 <br /> inches(762 mm),the working space shall be not less than the width of the <br /> equipment.No storage of any materials shall be located within the designated <br /> working space.Exceptions:1.Where other dimensions are required or allowed by <br /> NFPA 70.2.Access openings into attic or underfloor areas,which provide a <br /> minimum clear opening of 20 inches(509 mm)by 40 inches(1,016 mm). <br /> PASS 605.3.1 -Labeling Doors into electrical control panel rooms shall be marked with a plainly visible <br /> and legible sign stating ELECTRICAL ROOM or similar approved wording.The <br /> disconnecting means for each service,feeder or branch circuit originating on a <br /> switchboard or panelboard shall be legibly and durably marked to indicate its <br /> purpose unless such purpose is clearly evident. <br /> PASS 605.4.Multiplug adapters Multiplug adapters,such as cube adapters,unfused plug strips or any ocher <br /> device not complying with NFPA 70 shall be prohibited. <br /> P :eo a ,_^:i>)9=- <br /> Page8of12 <br />
The URL can be used to link to this page
Your browser does not support the video tag.