us <br />classified by <br />Underwriters Laboratories, Inc. <br />to UL 1479 and CANIULC-S115 <br />System No. W-L-5027 <br />ANSI/UL1479 (ASTM E814) CAN/ULC S115 <br />F Rating — 2 Hr <br />T Rating —1/2 Hr <br />L Rating At Ambient — Less Than 1 CFM/sq ft <br />L Rating At 400 F — Less Than 1 CFM/sq ft <br />F Rating — 2 Hr <br />FT Rating —112 Hr <br />FH Rating — 2 Hr <br />FTH Rating —1/2 Hr <br />L Rating At Ambient — Less Than 1 CFM/sq ft <br />L Rating At 400 F — Less Than 1 CFM/sq ft <br />SECTION A -A <br />1. Wall Assembly — The fire -rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner specified in the <br />individual U300, U400, V400 or W400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following <br />construction features: <br />A. Studs — Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) <br />lumber spaced 16 in. (406 mm) OC. Steel studs to be min 2-1/2 in. (64 mm) wide and spaced max 24 in. (610 mm) OC. <br />B. Gypsum Board* — Two layers of 5/8 in. (16 mm) thick gypsum wallboard, as specified in the individual Wall and Partition Design. Max diam <br />of opening is 6 in. (152 mm). <br />2. Metallic Sleeve — Nom 6 in. (152 mm) diam (or smaller) Schedule 40 (or thinner) steel pipe cast into wall assembly with joint compound and <br />installed flush with wall surfaces. <br />Reproduced by HILTI,.Inc. Courtesy of <br />Underwriters Laboratories, Inc. <br />Hilt! Firestop Systems January27, 2015 <br />rl— <br />N <br />O <br />to <br />1 of 2 <br />