Laserfiche WebLink
South Bend MPAC <br />ECM‐4 Replace chiller and schedule heat pumps back <br />Heating and Cooling Savings <br />Baseline AHU Operation <br />Supply Airflow, Cfm 27,500 <br />Ventilation Cfm - <br />% Ventilation 0% <br />Average Mixed air temp 68.0 <br />Setpoint 70.0 <br />Average Heating Btuhs 59,400 <br />Heating hours per year 6,899 <br />Natural Gas Consumed, therms / Yr 773 <br />Cooling return temp 77.0 <br />Cooling setpoint 75.0 <br />Average Cooling Btuhs 59,400 <br />Cooling hours per year 895 <br />Cooling Energy, kWh per year 7,198 <br />Proposed AHU Operation Occupied <br />Supply Airflow, Cfm 27,500 <br />Ventilation Cfm - <br />% Ventilation 0% <br />Average Mixed air temp 68.0 <br />Setpoint 70.0 <br />Average Heating Btuhs 59,400 <br />Heating hours per year 2,756 <br />Natural Gas Consumed, therms / Yr 309 <br />Cooling return temp 77.0 <br />Cooling setpoint 75.0 <br />Average Cooling Btuhs 59,400 <br />Cooling hours per year 721 <br />Cooling Energy, kWh per year 5,564 <br />Proposed AHU Operation unccupied <br />Supply Airflow, Cfm 27,500 <br />Ventilation Cfm - <br />% Ventilation 0% <br />Average Mixed air temp 66.0 <br />Setpoint 68.0 <br />Average Heating Btuhs 59,400 <br />Heating hours per year 3,851 <br />Natural Gas Consumed, therms / Yr 432 <br />Cooling return temp 79.0 <br />Cooling setpoint 77.0 <br />Average Cooling Btuhs 59,400 <br />Cooling hours per year 135 <br />Cooling Energy, kWh per year 1,042 <br />Electric Savings, kWh 593 <br />Natural Gas Savings, Therms 33