Laserfiche WebLink
Light Duty Cast Iron <br />Frame and Cover <br />(See Note 3)Grade <br />Inlet Ball <br />Valve <br />Outlet Ball <br />Valve <br />1", 1 1 2", or 2" <br />Meter <br />Direction <br />of Flow <br />12" Min.36" Max.4'-0" <br />(Square or Circular) <br />4"4" <br />1" Holes for <br />Drainage 6'-0" Min.6"Min.6"Precast Conc. Base <br />Gravel (INDOT No. 8) <br />Core Holes <br />for Piping (Typ.) <br />(See Note 2) <br />Precast Conc. <br />6" <br />Min. <br />6" <br />Min.6"Min.Link Seal (Typ.) or <br />Approved Equal <br />Type "K" Copper Pipe <br />NOTES: <br />1. Precast Conc. structure shall be manufactured and installed in compliance with <br />ASTM C-478 (round str.) or ASTM C-913 (rectangular/square str.) <br />2. The cored opening shall be large enough to allow passage of the pipe flange. <br />3. Lid shall have the word "WATER" cast into it. If placed in a paved area, casting <br />shall be heavy duty. <br />SECTION VIEW <br />Curb Stop Valve and Box <br />Street Sidewalk <br />1", 1 1 2", or 2" Meter <br />Inlet Ball Valve <br />Outlet Ball ValveCurb Stop Valve and Box <br />Direction <br />of Flow <br />PLAN VIEW 2'-0"10" Clearance (Typ.) <br />24" Min. <br />Clearance <br />6/26/18 <br />CITY OF SOUTH BENDItemRevision <br />STANDARD <br />EFFECTIVE DATE: <br />REF STD SPEC SEC <br />APPROVED/REVISED BY THE BOARD OF PUBLIC WORKS <br />STANDARDS FOR DESIGN <br />AND CONSTRUCTION <br />Kara M. Boyles, Ph.D., P.E. Date <br />METER PIT SPECS. FOR 1", 1 1/2", AND 2" METERS 5-13 <br />5-2.7 <br />June 26, 2018 <br />SECTION 5 - WATER WORKS