Laserfiche WebLink
F.) I�:t,' JORlS11. IQC ACID <br />A. GENERAL <br />i. The Fluorisilicic Acid supplied under these specifications shall be clean and <br />free of visible suspended matter and shall not contain more than 0.020 percent <br />of the "heavy metals", mercury, lead, bismuth and copper expressed as lead <br />(Pb); and shall contain no soluble mineral or organic substances in quantities <br />capable of a deleterious or injurious effect upon the health of those consuming <br />water that has been treated properly with fluorsilicic acid. <br />ii. Product to meet the latest AWWA standard for Fluorisilicic Acid (B703). <br />iii. Price is to be based on a 23% solution. <br />iv. Bidders shall quote price per pound. <br />B. DELIVERY <br />The vendor shall deliver bulk fluoride to the following well locations in the <br />quantities as specified by a representative of the South Bend Water Works. <br />ii. 23% Fluorisilicic Acid delivered in tank truckloads. <br />iii. Deliveries are estimated at thirteen (13) tank trucks with two to four stop -offs <br />per 20,000 lb. load. <br />iv. No stop -off or fuel surcharges allowed however, demurrage charges will be <br />allowed after 2 hours per stop. <br />V. Suppliers must furnish own unloading hose at least 40 feet in length with <br />proper couplings to hook onto two male N.P.T., and must blow off hose to <br />bulk tank at each stop. <br />vi. City will not accept delivery of more than 10% over the order quantity. <br />vii. Delivery Locations: <br />