AME�RESCO40 <br />Gret..,lrm - COean m u%tanalbla <br />Verificationof SavI — The savings for this ECM were reviewed following the ECM Construction and <br />Performance Verification plan as defined in Exhibit G-1 of the Amendment. The savings have been achieved <br />based on completion of the upgrade. Upon delivered functional capability as documented during the <br />commissioning and closeout process, the savings associated with the controls upgrade were deemed achieved. <br />The new controls system was commissioned during project closeout to confirm that all of the equipment was <br />being controlled as expected. The building automation system was used to verify that the control strategies <br />were implemented and operating as expected. Additionally, the project site was surveyed to confirm that the <br />equipment was installed in conformance with the Scope of Services. <br />Ameresco has remotely monitored the building automation system during the performance period. While the <br />data indicates that the equipment is being controlled as anticipated, the building schedules are exceeding the <br />expected operating hours per week. As shown in Exhibit G-1 of the Amendment, the expected daily equipment <br />operation was 6AM-6PM Monday -Friday, or 60 hours per week. The screenshot below shows that the <br />equipment is currently operating 114 hours per week. It is recommended that the building schedules be <br />reduced as close as possible to 60 hours per week of operation so that the full value of this ECM can be realized. <br />WV klyachedu!e Special E—t. I Summery <br />t ; Jfl <br />® a <br />Hendricks Counl ,IN <br />Sun Igor Iue !,Ned Thu n ,_sal. <br />March 2V1, 2019 <br />M <br />Em <br />City of South lBend August 27, 2019 40 11. Measurement g Verification <br />Tacfe content is subject to ConfidentialltV Restrictions" <br />