Laserfiche WebLink
residual and for no less than twenty-four (24) hours at <br />140 degree F. <br />2. The City reserves the right to run performance tests once <br />a month. <br />3. Any product which, in the City's opinion, does not meet <br />the specified performance requirements or fails to <br />comply with the specifications will be disqualified. <br />D, COVERAGE <br />i. These specifications cover blends of phosphate compounds used to stabilize or <br />sequester soluble iron and manganese in potable water. <br />E. PHYSICAL FORM <br />i. Product shall be a granular form. Powdered material will not be accepted. <br />F. PHYSICAL STANDARDS <br />i. Phosphate blend shall comply with the following physical requirements: <br />1. Color: White <br />2. Solubility: Completely miscible in water <br />3. Percent Phosphate as PO4 Minimum of 80% <br />4. Physical Form: Granular <br />G. CHEMICAL STANDARDS <br />i. Phosphate blend shall contain only NSP approved phosphorous ingredients. <br />ii. No amines or other chelating agents shall be used. <br />iii. Blended phosphate product formulation shall be only sodium salts of <br />phosphate compounds. <br />iv. No potassium salts shall be used. <br />V. Impurities in polyphosphate products shall not exceed the following <br />concentrations: <br />ArsenicasAS .. ........... ... O1 m if <br />Copper asmmCUmm m0.2 <br />Heavy Metals (total as Pb) 0.001 mg/1 <br />Iron FE 0.1 MR/1 <br />Man anese as MN < .05 mg/1m <br />Organics as..,C ......._..._....... . None..... <br />Silica as S1O2 1.0 <br />Zinc as ZN 0 01 m /l <br />