Laserfiche WebLink
4.0 EQUIPMENT SPECIFICATIONS <br />4A SOFTENER TANK(S) <br />Each softener tank shall be 18 in, in diameter. The overall tank height (less base) shall be 65 in,, sufficient to <br />allow for a proper freeboard space above the resin bed for adequate expansion of the resin during <br />backwashing. <br />4.1,1 Tank Construction <br />Tank(s) shall be manufactured of polyester reinforced by a continuous roving glass filament overwrap. The top <br />opening will be 4"-8 UN threaded and the tank bottom will be supported on a molded structural base. <br />4.1.2 Access Openings (Optional) <br />Each tank will be equipped with openings for mineral filling and periodic inspection. <br />4.2 INTERNAL DISTRIBUTION <br />4.2.1 The upper distribution system shall be of the single point diffuser type to dispense water laterally to avoid <br />channeling within the resin bed. <br />4.2.2 The lower distribution system shall be of the single point distributor type, constructed of PVC pipe and a fine <br />slotted strainer to provide even flow distribution through the resin bed. The distribution system shall be <br />embedded in a two layer subfill of washed Inorganic material to support the resin bed. <br />4.3 MAIN OPERATING VALVE <br />The main operating valve shall be of a top mount design constructed of thermoplastic resistant to attack by <br />substances found in natural water supplies. Inlet and outlet connections to be 1.5" or 2 inch NPTE. The Cv <br />(flow coefficient) of the main operating valve shall be equal to/greater than 32. <br />A vacuum breaker and pressure regulating valve shall be integrated in the design of the main operating valve. <br />The main operating valve will be of the motor driven, mechanically activated design with 5 positions to <br />accomplish the regeneration steps of backwash, brine draw/rinse, fast rinse and brine refill In addition to the <br />service position. The internal seals will be of a modular design for ease of replacement and service. <br />The main operating valve will be fitted with a fixed orifice eductor to control brine draw/slow rinse. <br />The main operating valve shall be designed by the same manufacturer as the water softener system and tested <br />prior to shipment, <br />4.4 FLOW CONTROL <br />The backwash flow controller shall be a pressure -compensating orifice capable of providing and maintaining <br />proper backwash flows over the entire listed operating pressure range of the system. The backwash flow <br />controller shall be easily serviced without special tools and design so that service to the flow controller can be <br />performed without disassembly of the valve body or the sequencing controller and without disconnecting <br />existing inlet and outlet piping connections. <br />4.5. CONTROLS <br />A fully integrated programmable microprocessor driven electronic controller shall be provided to automatically <br />cycle the main operating valve through the regeneration sequence, The electronic controller shall he designed <br />and manufactured by the same manufacturer as the water treatment equipment. <br />The controller shall be capable of initiating a regeneration by accepting an internal signal from the controller <br />time keeping device; an external Hall -Effect flow sensor, a Culligan Aqua -Sensor, an external device such as a <br />remote start push-button or any combination of these methods. The controller shall sequence all steps of an <br />automatic regeneration and automatically return the softener to a service or stand-by mode. The initiating time <br />and/or volume setpoints shall automatically reset upon completion of the regeneration sequence. <br />Page 2 of 5 <br />